INSTALLATION, USE AND MAINTENANCE MANUAL

 

 

 

 

 

 

 

   

 

 

 

 

 

DUCTO - SLC 

CANALIZED FANCOIL 

 

 

 

Summary of Contents for DUCTO - SLC

Page 1: ...ergie com Share capital int vers 150 000 Tax code VAT number 01827470228 REA registration nr 180610 Reg Companies TN 10656 Mechanographic number TN025148 www innovaenergie com Page 1 N420355A_Manuale...

Page 2: ...TS 8 1 10 DISASSEMBLY AND DISPOSAL 8 1 11 MAIN COMPONENTS UNITS 8 1 12 DIMENSIONAL 9 2 INSTALLATION 10 2 1 INSTALLATION CONDITIONS 10 2 2 UNIT POSITIONING 10 2 3 CONDENSATE DRAIN CONNECTION 11 3 AREAU...

Page 3: ...6 1 OPERATION VERSION S 25 6 2 OPERATION VERSION I 25 6 3 TURNING THE UNIT ON AND OFF 26 6 4 MODIFICATION OF FANS SPEED AND BOOSTER FUNCTION 26 6 5 AUTO FUNCTION 26 6 6 CHANGE OF SEASON 26 6 7 KEY LOC...

Page 4: ...Sales Department to receive further information or updates to the technical documentation and for any improvement proposals to this manual All reports received will be rigorously examined 1 2 BASIC SA...

Page 5: ...s the presence of moving parts and involves a risk of damage to exposed people 1 4 WARNINGS The unit must be installed by qualified and authorized personnel according to the regulations in force in th...

Page 6: ...th connection is made do not ground the appliance on distribution pipes Momentary surges of high intensity could damage the unit Installations performed outside the warnings of this manual or use outs...

Page 7: ...sale The removal deterioration and illegibility of the plate placed on the unit involves major problems in identifying the machine in the availability of spare parts and therefore in any future maint...

Page 8: ...t Check the power supply and grounding of the unit 1 10 DISASSEMBLY AND DISPOSAL Do not disassemble or dispose of the product yourself Disassembly demolition disposal of the product must be carried ou...

Page 9: ...1190 1477 B mm 550 750 950 1150 1437 C mm 240 240 240 240 240 D mm 695 695 695 695 695 AND mm 570 770 970 1170 1457 F mm 637 637 637 637 637 G mm 90 90 90 90 90 H mm 460 660 860 1060 1317 THE mm 150...

Page 10: ...n installation site where there is sufficient space around the unit for the connections of the air ducts and to be able to carry out maintenance operations the consistency of the ceiling wall floor wh...

Page 11: ...e for carrying out maintenance activities the opening of the unit cover front and accessibility to the electrical box and to the hydraulic connections must be guaranteed Do not mount the unit with the...

Page 12: ...positioning the drain is 18 mm in diameter In vertical positioning the drain is 20 mm in diameter Horizontal installation drain Vertical installation drain 3 AREAULIC CONNECTIONS 3 1 AREAULIC CONNECT...

Page 13: ...Air intake Aeraulic attacks Air delivery and return dimensions table SLC 400 600 800 1000 1200 TO Delivery Base x Height mm 510 x 150 710 x 150 910 x 150 1110 x 150 1370x150 B Shooting Base x Height m...

Page 14: ...cular inlets D Return plenum with circular inlets The two circular inlets of the unit are made with abs flanges and are 160 mm female diameter 3 Aeraulic attacks Air delivery and return dimensions tab...

Page 15: ...e to manage the air intake on the rear or front ceiling mounting lower front wall mounting To change the orientation proceed as in the figure to the side removing the screws from the air intake panel...

Page 16: ...y do not contain foreign materials such as sand stones rust flakes welding drops slag etc Otherwise wash the hydraulic circuit by bypassing the unit Absolutely avoid pump cavitation and the consequent...

Page 17: ...ny case be careful not to rotate or twist the pipes coming from inside the unit Rotating the pipes during connection could damage the connections inside the unit and cause water leaks during operation...

Page 18: ...the maximum load that can be reached The relative data are indicated on the attached wiring diagram and on the unit identification plate IS It is forbidden to enter the unit with electric cables unle...

Page 19: ...C COMMAND S versions wiring diagram CONNECTIONS BY THE CUSTOMER L N PE Power supply 230 1 50 Check power in the previous tables 10v Reference voltage signal Voltage supplied by the motor I max 20 ma Y...

Page 20: ...ontact closed Unit on CP Contact presence Contact closed unit off CHILLER Generator pump consent Clean Contact hot cold request activation WATER VALVE N EV1 Water valve post battery Live contact 220v...

Page 21: ...network and management of the unit through a dedicated APP The controls can be supplied in both White and Black colors The control is connected to the unit via a 0 75 1mm 4 conductor shielded braided...

Page 22: ...cable with a maximum length of 150 m Carry out a layout in order to minimize the length of the leads terminate the line with the supplied 120 resistor do not make star connections the connection with...

Page 23: ...3 way valve with dedicated cable and connector The pre wired connector is connected to the terminals on the electronic board N Neutral EV1 Opening command Water valve connection GENERATOR CONNECTION T...

Page 24: ...unit connection MODBUS RTU CONNECTION TO REMOTE PANEL T H With the connection of the remote panel the machine can be connected to a supervision system directly on the control panel which becomes a sla...

Page 25: ...olled by the user through the wall mounted touch control EEA649II EEB649II EFA649II EFB649II it is possible to connect humidity regulator and air quality regulator sensors The keys present in the main...

Page 26: ...p constant As the system pressure drops vary Fan speed management 6 5 AUTO FUNCTION By pressing the auto key the unit will work in automatic mode According to the detected temperature and the set temp...

Page 27: ...All adjustments are disabled for the user and bL appears when any key is pressed By repeating the sequence the keys are unlocked bL Key lock 6 8 PANEL BRIGHTNESS ADJUSTMENT With the panel off keep th...

Page 28: ...ted knobs If the conditions of the filters allow it they can be cleaned using a vacuum cleaner or a low pressure compressor WITH AIR INTAKE PLENUM If the air intake plenum accessory is present the fil...

Page 29: ...nect the condensate drain pipe open the unit cover by releasing the screws on it check and if necessary clean the fans the condensate drain and the walls close the cover and lock the fixing screws For...

Page 30: ...nger Clean the filters Increase the rotation speed Clean pipes or exchanger Insufficient efficiency of the exchanger Exchanger fins clogged No water flow Clean the surfaces of the exchanger Check the...

Page 31: ...of an alarm has two display modes an error code present on the EEA649II EEB649II EFA649II EFB649II command a led on the electronic board that shows a flashing sequence with the type of alarm present...

Page 32: ...n alarm Faulty fan connector or no feedback signal Check the connection of the fan connector to the board Replace the fan control cable 2 flashes off 3 seconds Water probe alarm Broken or missing read...