background image

© MASS ELECTRONICS Pty Ltd  2005

Models:

IRM5004:  4 Channel Relay Module 
IRM5008:   8 Channel Relay Module

Specifications

Power Supply

Voltage:    

24VAC ±10% @ 50/60Hz OR

Power Consumption: 5VA Max.

The operating voltage must meet the requirements of Safety Extra Low Voltage (SELV) to 
EN60730. The transformer used must be a 

Class 2 safety transformer

 that has the energy 

and voltage limiting characteristics as described in the National Electrical Code, ANSI/
NFPA70. It must also be sized and fused in compliance with local safety regulations.

Input

IRM5004   

Four 0-10VDC Control Inputs

IRM5008   

Eight 0-10VDC Control Inputs

Outputs

N/O voltage free contacts (2A max. @ 24VAC)

Power Terminal Identification

24V 

24VAC Supply

0V 

Common and 0VAC Supply (x2)

Input Terminal Identification

1 to 8 

Individual Control Signals

Com 

Control Signal Common

Relay Terminal Identification

IRM5004

A, C, E, G   

Normally Open Relay Outputs

B, D, F, H   

Relay Common

IRM5008

A, C, E, G, I, K, M, O  Normally Open Relay Outputs

B, D, F, H, J, L, N, P  Relay Common

Temperature Ratings

Storage:   

0-50°C non-condensing

Operating: 

0-40°C non-condensing

Enclosure 

Manufactured from an ignition resistant grade of ABS which meets 

the requirements of AS2420.

Colour:  

Grey

Mounting:  

DIN rail mounted

Installation

1. Mount controller is a dry and reasonably clean location free or 

excessive vibration.

2. Fit to DIN Rail.

3. Wire in accordance with INNOTECH connection diagrams and 

local bylaws or refer to your local distributor.

Wiring

1. Earth one side of the 24VAC at the transformer.

2. Connect the EARTHED side of the 24VAC to the 0V terminal.

3. Connect the remaining side of the transformer to the 24V 

terminal.

DS 3.13

 

August 2013

  

IRM500x

Relay Modules

Application

The INNOTECH range of Relay Modules are designed for applications 

where up to eight individual 0-10VDC control signal inputs are 

required to control up to eight individual stages of heating or cooling 

in air conditioning and associated systems. The switching threshold 

for the control signals are as in the table below.

Channel

ON

OFF

1

2.5

0.5

2

5

2.5

3

7.5

5

4

9.5

7.5

5

2.5

0.5

6

5

2.5

7

7.5

5

8

9.5

7.5

Features

•  Factory set ON/OFF points need no adjustment

•  Reduced commissioning time

•  LED indication of relay status

•  The INNOTECH enclosure saves space and reduces installation 

time

Approved

The Innotech Relay Module conforms to:

•  EN 55011 Class B Group 1 & AS/NZS 2064:1997 for RCM labelling

•  FCC Title 47 CFR, Part 15 Class A for FCC Marking

•  UL listed to UL916, File Number E242628