© MASS ELECTRONICS Pty Ltd 2005
Models:
IRM5004: 4 Channel Relay Module
IRM5008: 8 Channel Relay Module
Specifications
Power Supply
Voltage:
24VAC ±10% @ 50/60Hz OR
Power Consumption: 5VA Max.
The operating voltage must meet the requirements of Safety Extra Low Voltage (SELV) to
EN60730. The transformer used must be a
Class 2 safety transformer
that has the energy
and voltage limiting characteristics as described in the National Electrical Code, ANSI/
NFPA70. It must also be sized and fused in compliance with local safety regulations.
Input
IRM5004
Four 0-10VDC Control Inputs
IRM5008
Eight 0-10VDC Control Inputs
Outputs
N/O voltage free contacts (2A max. @ 24VAC)
Power Terminal Identification
24V
24VAC Supply
0V
Common and 0VAC Supply (x2)
Input Terminal Identification
1 to 8
Individual Control Signals
Com
Control Signal Common
Relay Terminal Identification
IRM5004
A, C, E, G
Normally Open Relay Outputs
B, D, F, H
Relay Common
IRM5008
A, C, E, G, I, K, M, O Normally Open Relay Outputs
B, D, F, H, J, L, N, P Relay Common
Temperature Ratings
Storage:
0-50°C non-condensing
Operating:
0-40°C non-condensing
Enclosure
Manufactured from an ignition resistant grade of ABS which meets
the requirements of AS2420.
Colour:
Grey
Mounting:
DIN rail mounted
Installation
1. Mount controller is a dry and reasonably clean location free or
excessive vibration.
2. Fit to DIN Rail.
3. Wire in accordance with INNOTECH connection diagrams and
local bylaws or refer to your local distributor.
Wiring
1. Earth one side of the 24VAC at the transformer.
2. Connect the EARTHED side of the 24VAC to the 0V terminal.
3. Connect the remaining side of the transformer to the 24V
terminal.
DS 3.13
August 2013
IRM500x
Relay Modules
Application
The INNOTECH range of Relay Modules are designed for applications
where up to eight individual 0-10VDC control signal inputs are
required to control up to eight individual stages of heating or cooling
in air conditioning and associated systems. The switching threshold
for the control signals are as in the table below.
Channel
ON
OFF
1
2.5
0.5
2
5
2.5
3
7.5
5
4
9.5
7.5
5
2.5
0.5
6
5
2.5
7
7.5
5
8
9.5
7.5
Features
• Factory set ON/OFF points need no adjustment
• Reduced commissioning time
• LED indication of relay status
• The INNOTECH enclosure saves space and reduces installation
time
Approved
The Innotech Relay Module conforms to:
• EN 55011 Class B Group 1 & AS/NZS 2064:1997 for RCM labelling
• FCC Title 47 CFR, Part 15 Class A for FCC Marking
• UL listed to UL916, File Number E242628