DS 13.01 - ICS0x - Innotech Control Station

September 2013

Specifications

Power Supply

•  Voltage:  

 

24VAC ±10% @ 50/60Hz

•  Power Consumption:  

3VA max

Inputs

•  Push buttons for adjusting control values

•  Push button for momentary input of “digital function”

Outputs

•  No physical outputs

•  Display of Temperature and Setpoint

Terminal Identification

24VAC Supply

0VAC Supply

3 Earth

Terminal 3 is for the protection of the Comms circuitry and must 

be connected to a good electrical bonded Earth.  

COMMS Connection

S1 

Shield from incoming Comms Cable.

RS485 (+) signal.

RS485 (-) signal.

S2 

Shield from outgoing Comms Cable.

 

Do not connect.  Only used on REM Networks

      

Temperature Ratings

•  Storage 

0 to 50°C non-condensing

•  Operating 

0 to 40°C non-condensing

Enclosure

The Innotech Control Stations are housed in switchplate that 

mounts in standard electrical wall plates.

Colour:    

White

Mounting:  

Wall mounted

Innotech Controller Configuration

The interface to the Innotech Control Station is with the use of 

Global Blocks in the configs executed on Innotech Controllers 

(Genesis and Maxim families). The Innotech Control Stations have 

the following pre-defined Global Blocks:

•  CS:xxx AI Set Point Adjust

•  CS:xxx AO Temperature Display

•  CS:xxx DI On/Off 

•  CS:xxx DO Run Status

•  CS:xxx FS (ICS02 Only) Fan Speed (0, 1, 2, 3)

xxx represents the three digit address. (ie. Address 10  is 010, 

Address 5 is 005)

To access the points on the Innotech Control Station, Global Blocks 

with names corresponding to the above names need to be placed 

in the config. The figure below provides an example for an ICS02 at 

network address 2: