![Innon Link IO Manual Download Page 20](http://html.mh-extra.com/html/innon/link-io/link-io_manual_2062919020.webp)
Document name: Link IO - Manual
Document date: 1.2 10/02/2020
20
For every Universal Channel configured as
“Output” it is possible to configure the desired output in case the
Watchdog function is used and enabled
In the example below, Universal Channels 4, 5, 8 and 10 are configured as outputs. In case of the watchdog
function driving the outputs, Universal channel 4 would go to 0%, channel 5 to 50% and channels 8 and 10
would go to 100% full output
Digital Outputs
The digital outputs are driven by relays.
For every Digital Output it is possible to configure the desired status in case the Watchdog function is used
and enabled.
In the example below all the Digital Outputs are going to an “OFF” status in case of the Watchdog function
driving the outputs.
Note that output 6 provides a relay with both NO and NC contacts.
Analog Outputs (only main unit)
The main unit has 2 Digital Inputs and 2 Analog Outputs more compared to the expansion devices. The
Analog Outputs can be configured as 0-10V, PWM 100Hz or PWM 2kHz
For each Analog Output it is possible to configure the desired value in case the Watchdog function is used
and enabled. The settings are in the same screen of the Digital Output
In the example both analog output would go to 0% in case of the Watchdog function driving the outputs.