EDAM-4200 Series User’s manual Version 1.03
8.4.56
~AA5V
Sets the current DO value as power-on or safe value
Description: Set the current DO value as power-on or safe value
Command:
~AA5V [CHK](cr)
Syntax:
~
Command leading code
AA
Module address ID(01 to FF , Always 01)
5
command for sets the current value as the power-on DO value or the
safe DO value.
V
Set power-on value or safe value
= P - set power-on value,
= S - set safe value.
VVV
Timeout value in hex format from hex 001 to 28F .(unit 0.1 sec),
FF denotes 25.5 seconds
CHK
Check sum
(cr)
Carriage return
Response:
!AA (cr)
Valid command.
?AA[CHK](cr)
Invalid command
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Module address ID
CHK
Check sum
(cr)
Carriage return
Example 1: Set Safe value.
Set module DO to output value 2A.
Command:
@012A(cr)
Response:
>(cr)
Set current output value 2A as safe value.
Command:
~015S(cr)
Response:
!01(cr)
Read safe value and return safe value 2A.
Command:
~014S(cr)
Response:
!01002A(cr)
Example 2: S
et Power on value
Set module to output value 15.
Command:
@0115(cr)
Response:
>(cr)
Set current output value 15 as power-on value.
Command:
~015P(cr)
Response:
!01(cr)
Read Power on value and return power-on value 0015.
Command:
~014P(cr)
Response:
!010015(cr)
Ref. command:
~**, ~AA1, ~AA0, ~AA4V, ~AA2, ~AA3PPP , ~AA3P, ~AA3EVVV
Printed Date: 27 February 2018
143