EDAM-4200 Series User’s manual Version 1.03
8.4.45
$AAECN
Start/Stop single DI counter
Description: Start/Stop single digital input counter (Falling Edge Trigger)
Command:
$AAECN [CHK](cr)
Syntax:
$
Command leading code
AA
Module address ID (01 to FF , Always 01)
E
Represents enable/disable DI counter command
C
Represents DI counter channel number (0~F)
N
Represents Start/Stop option (=0 –Stop, =1 -Start)
CHK
Check sum
(cr)
Carriage return
Response:
!AA (cr)
Valid command.
?AA[CHK](cr)
Invalid command
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Module address ID
CHK
Check sum
(cr)
Carriage return
Example 1:
Start DI(2) counter
command:
$01E2
1
(cr)
response:
!01(cr)
Example 2:
Stop DI(2) counter
command:
$01E2
0
(cr)
response:
!01(cr)
Ref. command:
$AA0MCC, $AAECN, $AA0MCC(data1)(data2)
Printed Date: 27 February 2018
131