EDAM-4200 Series User’s manual Version 1.03
8.4.27
@AA6ON
Read a single digital output channel
Description: Read status of a single digital output channel
Command:
@AA6ON [CHK](cr)
Syntax:
@
Command leading code
AA
Module address ID (01 to FF , Always 01)
6O
command to read status of a single digital output channel.
N
Channel number (0-F).
CHK
Check sum
(cr)
Carriage return
Response:
>DD [CHK](cr)
Valid command
?AA[CHK](cr)
Invalid command
>
Delimiter for valid command
?
Delimiter for invalid command
AA
Module address ID
DD
Represents the status you want to set to the specific channel.
= 00 – output Deactivate.
= 01 – output Activate.
CHK
Check sum
(cr)
Carriage return
Example:
Read DO(1) status
command:
@016O1(cr)
response:
>01(cr)
; 01 represents DO channel(1) is activated
Related command:
@AA, $AA6, @AA6, @AA6DDD , #AA00DD, #AA1NDD, @AA6DDDD, @AA6ONSS
Printed Date: 27 February 2018
112