EDAM-4200 Series User’s manual Version 1.03
8.4.24
#AA1NDD
Set a single Digital Output Channel
Description: Write a single digital output channel
Command:
#AA1NDD [CHK](cr)
Syntax:
#
Command leading code
AA
Module address ID (01 to FF , Always 01)
1
represents writing to a single DO channel command
N
Channel number (0-F).
DD
represents the status you want to set to the specific channel.
= 00 – output Deactivate.
= 01 – output Activate.
CHK
Check sum
(cr)
Carriage return
Response:
!AA [CHK](cr)
Valid command
?AA[CHK](cr)
Invalid command
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Module address ID
CHK
Check sum
(cr)
Carriage return
Example 1:
The command set digital channel 2 Activate (ON) status for the specific module at address 01h.
command:
#011201(cr)
response:
!01
Example 2:
The command set digital channel 2 Deactivate (OFF) status for the specific module at address 01h.
command:
#011200(cr)
response:
!01
Related command:
@AA, $AA6, @AA6, @AA6DDD , #AA00DD
Printed Date: 27 February 2018
109