EDAM-4200 Series User’s manual Version 1.03
8.4.20
~AADS
Read DI/O active state
Description: Read digital input/output active state.
Command:
~AADS [CHK](cr)
Syntax:
~
Command leading code
AA
Module address ID(01 to FF , Always 01)
DS
Command for read DIO active status
CHK
Check sum
(cr)
Carriage return
Response:
!AAMN [CHK](cr)
Valid command
?AA[CHK](cr)
Invalid command
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Module address ID
M
Digital input channel active values,
= 0 - represent input value=0 is activate (ON),
input value=1 is deactivate (OFF or OPEN).
(Default)
= 1 - represent input value=1 is activate (ON),
input value=0 is deactivate (OFF or OPEN).
N
Digital output channel active values,
= 0 - represent output value=1 is activate (ON),
output value=0 is deactivate (OFF).
(Default)
= 1 - represent output value=1 is deactivate (OFF),
output value=0 is activate (ON).
CHK
Check sum
(cr)
Carriage return
Example:
Ref. command ~AADSMN
Related command:
~AADSMN
Printed Date: 27 February 2018
105