If the zones are programmed to report tamper by zone, the 4K7 and 12K end-of-line resistors should be
connected as per Figure 2 below. The 4K7 and 12K resistors are not included with the panel but may
be obtained from your local distributor of IDS products.
Figure 2: Tamper per Zone Connection
P.I
.R
.
+
+
-
-
N/C
N/C
T
T
GROUND
ZONE
12V
ALARM
PANEL
12K
4K7
!
The operation of the tamper is as follows:
!
If a partition is not armed and a tamper condition occurs, the siren will not sound but a tamper
condition will be reported.
!
If a partition is armed and tamper condition occurs the alarm will register a zone violation and a
tamper condition will bereported.
!
Regardless of whether the partition is armed or not, if a zone is programmed as a priority/panic
zone, a tamper will register a panic condition as well a tamper condition.
!
The colour codes for the 12K and 4K7 resistors are as seen in Figure 3 below.
Figure 3: Resistors used for Tamper per Zone
Purple
Brown Orange
Red
12K
4K7
Yellow Red
4. Connecting the Telephone Communicator
Refer to Figure 1.
!
The integral communicator has built in lightning protection to protect it from lightning induced
transients. For optimum protection connect a low impedance earth to the communicator. A poor earth
will be ineffective and may result in damage to the communicator and alarm panel.
!
Always connect the telephone communicator in the line seizure mode. Never in parallel with the
telephone i.e. connect the telephone receiver to the communicator terminals marked “phone” and the
incoming line to the terminals marked “line”.