InGateway Documentation, Release 0.0.1
Signal: 10–19, indicating that signal and device operation are normal.
Signal: 20–31, indicating good signal.
1.2.2 2. Installation
2.1 Precautions
• Power supply requirements: 24 V DC (12–48 V DC). Pay attention to the voltage class. The rated
current is 0.6 A (1.2–0.3 A).
• Environment requirements: operating temperature –25°C to 75°C; storage temperature –40°C to 85°C;
relative humidity 5% to 95% (non-condensing). The temperature on the device surface may be high.
Install the device in a restricted area and assess the surrounding environment.
• Avoid direct sunlight and keep away from thermal sources or areas with strong electromagnetic inter-
ferences.
• Install the gateway product on an industrial DIN-rail.
• Check whether the required cables and connectors are installed.
2.2 Installing and Uninstalling the Device on a DIN-Rail
2.2.1 Installing with a DIN-Rail
Procedure:
• Step 1: Select an installation place and reserve enough space for installation.
• Step 2: Insert the upper part of the DIN rail seat onto the DIN rail. Grab the lower end of the device
and revolve it upward in the direction indicated by arrow 2 with gentle force, to insert the DIN rail
seat onto the DIN rail. Check that the device is installed reliably on the DIN rail, as shown in following
figure on the right.