ABH2015IQE01_ - Installation and Operation Manual
14.3. Connection process of the digital outputs
Follow the instructions below to connect the digital outputs:
Normally closed (NC)
Normally open (NO)
Digital output 1
J36 EXT RELAY 1
Digital output 2
J44 EXT RELAY 2
1. Loosen the corresponding cable gland
“2.7. Description of cable inlets”
, remove the cap and pass the
cable through it.
2. If you wish to use the Normally Open contact, connect the wiring in the NO and COM positions in the
J36
EXT
terminals.
1 RELAY
and/or
J44 EXT. 2 RELAY
as shown in the previous figure.
3. If you wish to use the Normally Closed contact, connect the wiring in the NC and COM positions in the
J36 EXT
terminals.
1 RELAY
and/or
J44 EXT. 2 RELAY
as shown in the previous figure.
4. Correctly tighten the packing glands to prevent losses to the protection class, verifying that the wiring is
not taut. Check that the connection is tight.
41
Connecting the digital outputs
Ingeteam