ABH2015IQE01_ - Installation and Operation Manual
18.2. Display
The following figure shows the main screen of the inverter and the meaning of each field.
10:23 AM
09/07/17
10:23 AM
09/07/17
a
b
c
d
e
f
g
h
a. Current time, hh:mm.
b. Current date, dd/mm/yy.
c. Storage system data. The voltage in volts,
current in amps and state of charge are
displayed alternately. If COM is shown in place
of these values, there is no communication
with the BMS for the Li-Ion battery.
d. PV array data. The voltage in volts and current
in amps of the PV array is shown alternately.
If the PV array is not available but the inverter
has started, the voltage of the DC bus is
displayed in volts.
e. Percentage of nominal power and reason for
power reduction, if present
(1)
f.
Consumption grid output data. The power
in Watts and the voltage in volts is shown
alternately.
g. Auxiliary genset input data. The power in
Watts and the voltage in volts of the auxiliary
genset is shown alternately.
h. This indicates that the system is operating
under the communication setting in grid
support mode. If the symbol flashes, this
means that communications with the
INGECON SUN EMS Board have been lost. As
a result, the display will switch to standby.
(1)
In the event that the inverter is connected to a grid or auxiliary generator and there is a power reduction,
the current power percentage and the most restrictive reason for the limitation are shown. If there is not power
limitation this percentage will not display. The different reasons for a power limitation are explained below,
indicated both with the letter viewed on the display and the code set by communications.
Reasons for the power limitation
Letter viewed on the
display
Code sent by
communications
Description
B
9
Batteries. Limitation due to the storage system state of charge or configuration.
C
1
Limitation caused by a setting sent through communications o by the self
consumption mode managed by the INGECON SUN EMS Board.
D
10
Power available Battery charge limitation from the genset due to the power
available. This power is calculated with the rated power in the case of the
generator, or the contracted power in the case of the grid, minus the power
consumed by the charges.
F
4
N/A
G
5
N/A
H
12
DC bus. Limitation due to high voltage in the internal DC bus.
L
13
N/A
M
6
Configuration. Battery charge limitation from the genset, defined by a user
setting.
N
15
N/A
P
16
N/A
R
14
Apparent power. Limitation due to rated apparent power in the unit.
S
7
Self consumption mode. Limitation due to the operation of the self consumption
mode managed by INGECON SUN STORAGE 1Play.
55
Display control
Ingeteam