ABH2015IQE01_ - Installation and Operation Manual
8. Connection of the storage system
This chapter explains the requirements and process for connecting the storage system wiring to the unit. Read
carefully before starting the connection process.
8.1. Safety instructions for connecting the storage system
CAUTION
Before you start to make the connections, make sure there is no voltage in the inverter. Verify that the AC
protection of the auxiliary genset and the DC protection of the storage system are open, as well as the PV array
and the consumption grid.
Do not switch on the power
to the unit until you have successfully made the rest of the connections and the unit
is closed.
When carrying out the connections, respect the polarities marked on the electronic card. If the connection is
performed incorrectly the inverter could be damaged
Ingeteam accepts no liability for any damages caused by an incorrect connection.
8.2. Wiring requirements for connecting the storage system
The wiring gauge for connecting the storage system is specified in the following table:
INGECON SUN STORAGE 1Play
Up to 32 A
Up to 40 A
Up to 50 A
Wiring gauge
4 mm
2
6 mm
2
10 mm
2
Wiring diameter
9 ~ 13 mm
Wiring stripping length (L*)
18 mm
L*
8.3. Use of ferrite cores
Two of the ferrite cores supplied must be used to connect the storage system. Turn each wire around twice, as
indicated in the following figure.
27
Connection of the storage system
Ingeteam