ABH2015IQE01_ - Installation and Operation Manual
2.3. Optional accessories
These units may include the following accessories:
•
Communication card.
•
INGECON SUN EMS Board.
Communication cards
There are different options for communicating the units. For more information consult the corresponding
communication accessories manual available at
.
There are several ways to achieve this communication with these units:
•
RS-485.
•
Ethernet TCP.
•
Wi-Fi TCP.
INGECON SUN EMS Board
The INGECON SUN EMS Board is a control and communication device used to manage the energy flows within self
consumption installations. This device is integrated inside the inverter.
2.4. EMC requirements
INGECON SUN STORAGE 1Play units are equipped with the necessary filtering elements to comply with
EMC requirements for domestic applications in order to prevent disturbances in other equipment outside the
installation.
2.5. Acoustic contamination
The unit produces a slight buzz when in operation.
Do not place it on light supports which might amplify this buzz. The mounting surface must be firm and
appropriate for the weight of the unit.
2.6. Specification table
3TL
6TL
Nominal power (up to 40 ºC)
3 kVA
6 kVA
Max. temperature for rated power
40 ºC
Maximum output fault current
< 26 A rms (60 ms)
< 40 A rms (60 ms)
Maximum output overcurrent protection
26 A rms
40 A rms
Storage system input (DC)
Voltage range with photovoltaic installed
(1)
40 ~ 300 V
Voltage range without photovoltaic installed
(1)
40 ~ 450 V
Maximum charge/discharge current
50 A
Battery type
Lead-Acid, Li-Ion
(2)
Communication with Li-Ion batteries
CAN Bus 2.0
PV array input (DC)
PV array maximum power
7.5 kWp
11.5 kWp
MPP Voltage range
(3)
330
(3)
~ 480 V
Maximum input voltage
(4)
550 V
Maximum input current
20 A
30 A
Maximum short circuit current
22 A
33 A
Maximum inverter backfeed current to the array
0 A rms
MPPT
1
Number of strings
2
Auxiliary genset input (AC)
Rated voltage
230 V
Voltage range
172 ~ 264 V
13
Unit description
Ingeteam