2 Connecting the battery pack to the inverter
The instructions to connect the battery pack to the inverter are described in the “Installation Manual of
Pylontech”
Please, take into account the following technical notes:
1) The inverter is turned OFF before connecting the battery pack to the inverter.
2) The battery circuit breaker is on the OFF position.
3) Connect the DC power wires with 6-10mm
2
.
4) Connect the CAN Communication wire.
2.1 Wiring of CAN communication wire
Pylontech batteries require a CAN communication wire to the ISS 1Play.
The ISS 1Play will send the necessary keep-a-live command to the Pylontech battery, which is needed to
keep its internal circuit breaker close. When the battery does not receive for 15 seconds such a command, its
internal circuit breaker opens.
The ISS 1Play uses a two-pin CAN BAT connector and the Pylontech uses a RJ45. The pin-out is the
following:
It is mandatory that the ISS 1PLAY has its display correctly connected. Otherwise, the Pylontech will open its
internal circuit breaker after 15 seconds.