INGECON SUN STORAGE 1Play

 

Technical Guide 

30/09/2019 

3/9

 

1  Introduction 

This document describes the process to configure the INGECON SUN STORAGE 1Play 3TL / 6TL 
(hereinafter, ISS 1Play) to work with PYLONTECH FORCE H1/H2 and POWERCUBE X1/X2 batteries. 

The PYLONTECH HV and ISS 1Play equipment can be used in the following type of 

single phase

 

installations: 

  Stand-alone installations 
  UPS(Back-up) installations 
  Self-consumption/Grid Support installations 

 

The minimum FW versions to work with the ISS 1Play and PYLONTECH HV are the following: 

Minimum Firmware Version used in the PYLONTEHC HV: 

  Force H1/H2   V1.3 
  Powercube X1/X2   V4.4 

The battery´s firmware is supplied by the qualified distributor of Pylontech. For further details, check the 
“Installation Manual of Pylontech”. 

Minimum Firmware Version used in the ISS 1Play: 

  Inverter: ABH1002AA 
  Display: ABH1003_Q 

The inverter FW versions can be found at the display or via the “Ingecon Sun Manager” software: 

Using Ingecon Sun Manager: 

The firmware version is indicated underneath the inverter serial number. 

Using the Display: 

MAIN MENU > MONITORING > FIRMWARE MONIT 

For further details, check the “Installation and Operation Manual”. 

In order to know the firmware version from the  inverter or the display, the user should check the last two 
characters from the given firmware code. This two characters are arranged in alphabetical order. 

For example, the firmware code ABH1002_Y represents a Y version, and the ABH1002AA code represents 
an AA version. In this case, the AA version is more updated than the Y version. 

The inverter and the display should be updated to the latest available firmware version that can be found at 

www.ingeteam.com

 

 

Francisco Javier F.J.A. Ancn Jimenez

2019.10.31 08:36:45

Firmante: 

CN=Francisco Javier F.J.A. Ancn [email protected]=com0.9.2342.19200300.100.1.25=ingeteamrenovables

Llave publica: 

RSA/2048 bits

Summary of Contents for INGECON SUN STORAGE 1Play 3TL

Page 1: ...working with PYLONTECH FORCE H1 H2 and POWERCUBE X1 X2 ABH2010IMC13_ Francisco Javier F J A Ancn Jimenez 2019 10 31 08 36 45 Firmante CN Francisco Javier F J A Ancn JimenezE francisco ancin ingeteam c...

Page 2: ...Black start function 5 4 Battery s firmware update 6 5 Setting the inverter 7 5 1 DC Battery type 7 6 Final check 8 7 Attachment I References 9 Francisco Javier F J A Ancn Jimenez 2019 10 31 08 36 45...

Page 3: ...he inverter FW versions can be found at the display or via the Ingecon Sun Manager software Using Ingecon Sun Manager The firmware version is indicated underneath the inverter serial number Using the...

Page 4: ...cation wire to the ISS 1Play The ISS 1Play will send the necessary keep a live command to the Pylontech battery which is needed to keep its internal circuit breaker close When the battery does not rec...

Page 5: ...3 After 30 seconds press and hold the red start button again for another 5 seconds 4 Then the inverter and battery should get powered Make sure that the display s screen is ON In this situation if the...

Page 6: ...ributor For further details check the Pylontech guideline supplied by the distributor A minimum firmware version is necessary to work with the Ingecon Sun Storage 1Play Force H1 H2 V1 3 Powercube X1 X...

Page 7: ...Lithium Pylontech Force H1 H2 or Settings 1 DC BATTERY TYPE Type of Battery Lithium Pylontech Powercube X1 X2 Figure 1 DC Battery selection on Ingecon Sun Manager Click on the Send button A screen inf...

Page 8: ...an be done using the Ingecon Sun Manager software package or through the display Using the Display MAIN MENU MONITORING BATTERY MONIT STATUS doesn t show BMS ERROR Using Ingecon Sun Manager OnLine Bat...

Page 9: ...un Manager Software Installation Manual of PYLONTECH Force series or Powercube series Ingecon Sun Training https www ingeconsuntraining info page_id 7049 Francisco Javier F J A Ancn Jimenez 2019 10 31...

Reviews: