ABK2027IQE01_A - Installation and Operation Manual
13.4.1. Configuring the synchronization
You can synchronize up to four inverters. This depends on the number of synchronized inverters, following the
connection diagrams from this section.
For synchronization, one of the inverters must be set as master and the rest as slaves. The configuration as master
or slave is done via the synchronization card of each inverter.
The synchronization card has a switch with which you can select the operating mode (master-slave). In the previous
figure, we show the switch´s position for both configurations.
MASTER
SLAVE
MASTER
SLAVE
MASTER
SLAVE
MASTER
SLAVE
MASTER
SLAVE
MASTER
SLAVE
The synchronization card configured as master
The synchronization card configured as slave
INFO
If this step is not done properly, it presents an alarm on the display.
94
Connection of the DCAC connections module