The torque should be 50 lb.in (5.6 Nm).
A
B
C
D
≤
0.27 in
≤
0.51 in
M6
A. Torx T30 bolt.
B. M6 washer.
C. Terminal. Hole diameter of M6, maximum thickness of 0.27 in (7 mm), maximum width of 0.51 in
(13 mm).
D. M6 Threaded busbar.
8.4.2. Making the ground connections via a terminal
1. Strip the cable according to the size of terminal to be used.
2. Crimping the terminal on the cable.
3. Clean the contact surfaces on both the terminal and the connection bar with a clean cloth and ethanol.
4. Connect the terminal to the connection bar using the bolts and washers supplied by Ingeteam with the
unit, respecting the torque specified.
5. Ensure the correct connection of the cable and terminal.
64
Ground connection
Ingeteam