Ingersoll-Rand Voyager TZ 150F Series Service Facts Download Page 17

RT-SVF69C-EN

17

Sequence of Operation

Failure and Override Modes

Certain failure and overriding conditions require special 
handling of the Supply Fan Speed on units configured with 
Single Zone VAV. See below for a list of these conditions:

Supply Fan Proving Failure - If a Supply Fan Proving 
failure is detected, the Supply Fan will be de-energized 
after 40s of run time and the Fan Speed output will go 
to 0 Vdc (0%).

Ventilation Override Mode - If a VOM goes active in 
which the Supply Fan is commanded ON (Purge, 
Pressurize, etc.), the Supply Fan will be energized and 
the Fan Speed output will ramp to 100%.

Zone Temperature Sensor Failure - If the Active Zone 
Temperature input goes out of range, the unit will 
discontinue all Heating, Cooling, and Dehumidification 
operation. 

Supply Air Temperature Sensor Failure - If the Supply 
Air Temperature input goes out of range, the unit will 
revert back to Full Airflow, Traditional CV control. The 
unit will call out a Supply Air Temperature Sensor 
Failure Alarm, the RTRM System LED will flash the 2-
blink error code, and the Zone Sensor Heat 
(Modulating Heat Only) and Cool LEDs will flash.

Frostat Failure - If a Frostat failure occurs, all active 
Heating, Cooling, and Dehumidification will be de-
energized immediately and the Supply Fan will ramp 
up to 100%.

Heat Failure (High Temp. Limit Trip) - If a unit 
configured with Gas Heat has a High Temp. Limit trip, 
the Supply Fan will be requested to remain ON and the 
Fan Speed output will ramp to full speed.

Variable Air Volume Applications 
(Traditional VAV)

Supply Air Temperature Control - 
Occupied Cooling and Heating

The RTRM is designed to maintain a selectable supply air 
temperature of 40°F to 90°F with a +/- 3.5°F deadband. 

Note:

To reduce the risk of coil freezing, it is not 
recommended to set the supply air temperature 
below 50°F.

In cooling, if supply air temperature is more than 3.5 
degrees warmer than the selected temperature, a stage of 
cooling will be turned “On” (if available). Then if the 
supply air temperature is more than 3.5 degrees cooler 
than the selected temperature, a stage of cooling will be 
turned “Off”. At very low airflows the unit may cycle stages 
“On” and “Off” to maintain an average discharge air 
temperature outside the 7 degree deadband.

If the unit has modulating heat, the unit can be made to do 
discharge heating with VAV control. This is done by 
placing a contact closure across the “Changeover Input” 
on the RTAM. During this mode, the unit will heat to the 
Supply Air Heating Se/- 3.5°F. During low load or 
low airflow conditions the actual temperature swing of the 
discharge air will likely be greater. 

The RTRM utilizes a proportional and integral control 
scheme with the integration occurring when the supply air 
temperature is outside the deadband. As long as the 
supply air temperature is within the setpoint deadband, 
the system is considered to be satisfied and no staging up 
or down will occur.

Supply Air Temperature Control with an 
Economizer 

The economizer is utilized to control the supply air cooling 
at +1.5°F around the supply air temperature setpoint range 
of 40°F and 90°F providing the outside air conditions are 
suitable. While economizing, the mechanical cooling is 
disabled until the economizer dampers have been fully 
open for three minutes. If the economizer is disabled due 
to unsuitable conditions, the mechanical cooling will cycle 
as though the unit had no economizer. 

VHR Relay Output

During unoccupied mode, daytime warm-up (DWU) and 
morning warm-up (MWU) the VFD will open to 100%. All 
VAV boxes must be opened through an ICS program or by 
the VHR wired to the VAV boxes. The RTRM will delay 
100% fan operation approximately 6.5 minutes when 
switching from occupied cooling mode to a heating mode.

Summary of Contents for Voyager TZ 150F Series

Page 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Page 2: ...ion which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage...

Page 3: ...rademarks of their respective owners Revision History Updated Performance Data section WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury All Inge...

Page 4: ...Heating 15 Low Ambient Operation 15 Clogged Filter Option 15 Ventilation Override 16 Emergency Stop 16 Phase Monitor 16 Low Pressure Control 16 High Pressure Cutout and Temperature Dis charge Limit 1...

Page 5: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F3 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Page 6: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F4 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Page 7: ...0 81 0 80 7 79 9 80 1 79 1 Steady State Efficiency 81 81 81 No Burners 1 1 1 No Stages 2 2 N A Gas Supply Line Pressure in wc 2 5 14 0 2 5 14 0 2 5 14 0 Natural Only Natural or LP minimum maximum Gas...

Page 8: ...43 2 08 762 2 22 779 2 37 796 2 52 813 2 67 4000 649 1 64 673 1 78 696 1 92 717 2 06 738 2 21 758 2 36 778 2 51 796 2 66 815 2 81 832 2 96 4500 662 1 87 686 2 02 709 2 18 731 2 33 752 2 49 772 2 65 79...

Page 9: ...98 747 2 11 766 2 25 783 2 40 800 2 55 816 2 70 4000 656 1 68 679 1 82 702 1 96 723 2 10 744 2 25 764 2 40 783 2 55 802 2 70 820 2 85 837 3 01 4500 670 1 92 694 2 08 717 2 23 738 2 39 759 2 55 780 2...

Page 10: ...ters a 2 MERV 8 Filter b 2 MERV 13 Filter b Std Economizer with OA RA Dampers c Low Leak Economizer with OA RA Dampers d Electric Heater Accessory kW e 100 OA 100 RA 100 OA 100 RA 5 12 14 27 36 54 72...

Page 11: ...control LPC1 the high pressure control HPC1 and the discharge line thermostat DLT1 are closed while simultaneously reducing the modulating compressor motor speed to allow a smooth transition in system...

Page 12: ...is running at its maximum capacity and the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open the RTRM energizes the second fix...

Page 13: ...r compartment protects against abnormally high leaving air temperatures The automatic reset fan fail limit located in the upper middle section of the indoor fan board protects against abnormally high...

Page 14: ...e a new control scheme comprised of 2 existing schemes that have been traditionally mutually exclusive DCV and OA CFM Compensation Units configured with DCV will invoke the new Demand Controlled Venti...

Page 15: ...heat units the unit will have the ability to control the discharge air temperature to the calculated discharge air heating setpoint in order to maintain the Zone Temperature to the Zone Heating setpo...

Page 16: ...rse rotation It has an operating input voltage range of 190 600 VAC and LED indicators for ON and FAULT There are no field adjustments and the module will automatically reset from a fault condition Lo...

Page 17: ...to set the supply air temperature below 50 F In cooling if supply air temperature is more than 3 5 degrees warmer than the selected temperature a stage of cooling will be turned On if available Then...

Page 18: ...ode or switched to the Cooling Mode the unit will revert to the cooling operation If an Occupied Heating Mode is selected the unit will only function within the DWU perimeters until the system is swit...

Page 19: ...l temperature swing of the discharge air will likely be greater Zone Temperature Unoccupied Heating While a building is in an unoccupied period as designated by a remote panel with night setback or IC...

Page 20: ...g mode Allow all compressors to run long enough for the pressures to stabilize 2 Measure the liquid line temperature of each circuit near the condenser coil after pressures stabilize 3 Measure the liq...

Page 21: ...105F OD Ambient 95 F OD Ambient 85 F OD Ambient 74 62 F ID WB DB 86 72 F ID WB DB 120F OD Ambient 115F OD Ambient Figure 2 Cooling cycle pressure curve system 2 100 200 300 400 500 600 700 100 120 14...

Page 22: ...ve curve value c OK if the sub cooling is within 5 F of the curve value 4 The standard superheat operating range for units with the standard offering thermal expansion valves is 16 F 24 F These superh...

Page 23: ...RT SVF69C EN 23 Refrigerant Circuit Figure 4 12 5 tons eFlex system schematic...

Page 24: ...and protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingers...

Reviews: