BAS-SVP09F-EN
19
BACnet Data Points and Configuration Property
Definitions
The BCI-R device allows an ReliaTel control system to communicate with BACnet systems and
devices using BACnet MS/TP. This section includes information about:
•
BACnet protocol implementation conformance statement (PICS).
•
Object types: descriptions and configuration.
•
BACnet protocol: data link layers, device address binding, networking options, and character
sets.
•
Object data points and configurations.
BACnet Protocol Implementation Conformance Statement (PICS)
Standardized Device Profile (Annex L)
Profile Description
Supported Profile
BACnet Advanced Application Controller (B-AAC)
□
BACnet Application Specific Controller (B-ASC)
⌧
BACnet Building Controller (B-BC)
□
BACnet Operator Workstation (B-OWS)
□
BACnet Smart Actuator (B-SA)
□
BACnet Smart Sensor (B-SS)
□
Interoperability Building Blocks (Annex K)
Data Sharing Description
Supported BIBB
Data Sharing-ReadProperty-A (DS-RP-A)
⌧
Data Sharing-ReadProperty-B (DS-RP-B)
⌧
Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
⌧
Data Sharing-WriteProperty-A (DS-WP-A)
⌧
Data Sharing-WriteProperty-B (DS-WP-B)
⌧
Data Sharing-WritePropertyMultiple-B (DS-WPM-B)
⌧
Alarm and Event Management Description
Supported BIBB
Alarm and Event-ACKI-B (AE-ACK-B)
⌧
Alarm and Event-Alarm Summary-B (AE-ASUM-B)
⌧
Alarm and Event-Information-B (AE-INFO-B)
⌧
Alarm and Event-Notification Internal-B (AE-N-I-B)
⌧
Trending Description
Supported BIBB
Trending-Automated Trend Retrieval-B (T-ATR-B)
⌧
Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)
⌧
Device Management Description
Supported BIBB
Device Management-Backup and Restore-B (DM-BR-B)
⌧
Device Management-Device Communication Control-B (DM-DCC-B)
⌧