Table 29.
Freeze protection heater summary
Heater
Thermostat
Jumper
Heater Description
Heaters
Evap and Water Pipe Heaters
6B52
6X1-2 to 6X1-3
Evaporator
6E50–1
Evap Entering Water
6E50–3
Evap Leaving Water
6E50–2
Pump Package (optional)
6B53
6X2-2 to 6X2-4
6X2–3 to 6x2–5
Water Pump Piping
6E51–1, 6E51–2, 6E51–3,
6E51–4, 6E51–5
Note:
Not all heaters are present on all unit configurations. See schematics and component locations in AC-SVE002*-EN.‘
3. Once unit is secured, perform tasks as outlined in
the Maintenance chapter.
Seasonal Unit Start-up
Procedure
1. PRIOR to water being pumped into system, use
gauges to verify positive pressure in the evaporator
and condenser. Lack of pressure could indicate a
system leak. In the event that no pressure is
present, contact local Trane service.
2. Close all drain valves and re-install the drain plugs
in the evaporator.
3. Service the auxiliary equipment according to the
start-up/maintenance instructions provided by the
respective equipment manufacturers.
4. Close the vents in the evaporator chilled water
circuits.
5. Open all the valves in the evaporator chilled water
circuits.
6. Open all refrigerant valves or verify they are in the
open condition.
7. If the evaporator was previously drained, vent and
fill the evaporator and chilled water circuit. When
all air is removed from the system (including each
pass), install the vent plugs.
8. Check the adjustment and operation of each safety
and operating control.
9. Refer to the sequence for daily unit startup for the
remainder of the seasonal startup.
System Restart After Extended
Shutdown
N
NO
OT
TIIC
CE
E
E
Eq
qu
uiip
pm
me
en
ntt D
Da
am
ma
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o ffo
ollllo
ow
w iin
nssttrru
uccttiio
on
nss cco
ou
ulld
d rre
essu
ulltt iin
n
e
eq
qu
uiip
pm
me
en
ntt d
da
am
ma
ag
ge
e..
E
En
nssu
urre
e tth
ha
att tth
he
e cco
om
mp
prre
esssso
orr a
an
nd
d o
oiill ssu
um
mp
p h
he
ea
atte
errss
h
ha
av
ve
e b
be
ee
en
n o
op
pe
erra
attiin
ng
g p
prro
op
pe
errlly
y ffo
orr a
a m
miin
niim
mu
um
m o
off 2
24
4
h
ho
ou
urrss b
be
effo
orre
e sstta
arrttiin
ng
g..
Follow the procedures below to restart the unit after
extended shutdown:
1. Check refrigerant pressure as noted in Seasonal
Unit Start-Up procedure.
2. Verify that the liquid line service valves, oil line,
compressor discharge service valves and suction
service valves are open (backseated).
N
NO
OT
TIIC
CE
E
C
Co
om
mp
prre
esssso
orr D
Da
am
ma
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o ffo
ollllo
ow
w iin
nssttrru
uccttiio
on
nss b
be
ello
ow
w cco
ou
ulld
d cca
au
usse
e
cca
atta
assttrro
op
ph
hiicc d
da
am
ma
ag
ge
e tto
o tth
he
e cco
om
mp
prre
esssso
orr..
D
Do
o n
no
ott lle
ea
av
ve
e o
oiill lliin
ne
e ssh
hu
utt o
offff v
va
allv
ve
e o
orr tth
he
e iisso
olla
attiio
on
n
v
va
allv
ve
ess ccllo
osse
ed
d o
on
n u
un
niitt sstta
arrtt--u
up
p..
3. Check the oil sump level. See instructions in
Maintenance chapter.
4. Fill the evaporator water circuit. Vent the system
while it is being filled. Open the vent on the top of
the evaporator and condenser while filling and
close when filling is completed.
N
NO
OT
TIIC
CE
E
P
Prro
op
pe
err W
Wa
atte
err T
Trre
ea
attm
me
en
ntt R
Re
eq
qu
uiirre
ed
d!!
T
Th
he
e u
usse
e o
off u
un
nttrre
ea
atte
ed
d o
orr iim
mp
prro
op
pe
errlly
y ttrre
ea
atte
ed
d w
wa
atte
err
cco
ou
ulld
d rre
essu
ulltt iin
n sscca
alliin
ng
g,, e
erro
ossiio
on
n,, cco
orrrro
ossiio
on
n,, a
allg
ga
ae
e o
orr
sslliim
me
e..
U
Usse
e tth
he
e sse
errv
viicce
ess o
off a
a q
qu
ua
alliiffiie
ed
d w
wa
atte
err ttrre
ea
attm
me
en
ntt
ssp
pe
ecciia
alliisstt tto
o d
de
ette
errm
miin
ne
e w
wh
ha
att w
wa
atte
err ttrre
ea
attm
me
en
ntt,, iiff
a
an
ny
y,, iiss rre
eq
qu
uiirre
ed
d.. T
Trra
an
ne
e a
assssu
um
me
ess n
no
o rre
essp
po
on
nssiib
biilliitty
y
ffo
orr e
eq
qu
uiip
pm
me
en
ntt ffa
aiillu
urre
ess w
wh
hiicch
h rre
essu
ulltt ffrro
om
m u
un
nttrre
ea
atte
ed
d
o
orr iim
mp
prro
op
pe
errlly
y ttrre
ea
atte
ed
d w
wa
atte
err,, o
orr ssa
alliin
ne
e o
orr b
brra
acckkiissh
h
w
wa
atte
err..
5. Close the fused-disconnect switches that provides
power to the chilled water pump.
6. Start the evaporator water pump and, while water
is circulating, inspect all piping for leakage. Make
any necessary repairs before starting the unit.
7. While the water is circulating, adjust the water
flows and check the water pressure drops through
the evaporator. See Evaporator Waterside Pressure
Drop Curves in Installation Mechanical chapter, and
water flow rates in General Data tables..
8. Verify proper operation of flow switch on the