AC-SVX002C-EN
19
Center of Gravity
Figure 4. Center of gravity
END VIEW
(Non-Control Panel End)
Z
Y
CG
SIDE VIEW
X
CG
C
o
n
t
r
o
l
P
a
n
e
l
Table 4. Center of gravity — shipping
Unit
Size
CGx
CGy
CGz
CGx
CGy
CGz
in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
Standard Unit (without Pump Package)
Unit with Pump Package Option
140
86
2184
46
1168
39
991
107
2718
46
1168
34
864
160
86
2184
46
1168
39
991
107
2718
46
1168
34
864
180
108
2743
47
1194
39
991
132
3353
47
1194
35
889
200
108
2743
47
1194
39
991
132
3353
47
1194
35
889
215
123
3124
47
1194
41
1041
154
3912
47
1194
36
914
230
122
3099
47
1194
41
1041
153
3886
47
1194
36
914
Table 5. Center of gravity — operating
Unit
Size
CGx
CGy
CGz
CGx
CGy
CGz
in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
Standard Unit (without Pump Package)
Unit with Pump Package Option
140
87
2210
46
1168
39
991
107
2718
46
1168
34
864
160
87
2210
46
1168
39
991
107
2718
46
1168
34
864
180
109
2769
47
1194
39
991
132
3353
47
1194
35
889
200
109
2769
47
1194
39
991
132
3353
47
1194
35
889
215
123
3124
47
1194
41
1041
154
3912
47
1194
36
914
230
122
3099
46
1168
41
1041
153
3886
47
1194
36
914
Isolation and Sound Emission
The most effective form of isolation is to locate the unit
away from any sound sensitive area. Structurally
transmitted sound can be reduced by elastomeric
vibration eliminators. Spring isolators are not
recommended. Consult an acoustical engineer in
critical sound applications.
For maximum isolation effect, isolate water lines and
electrical conduit. Wall sleeves and rubber isolated
piping hangers can be used to reduce the sound
transmitted through water piping. To reduce the sound
transmitted through electrical conduit, use flexible
electrical conduit.
State and local codes on sound emissions should
always be considered. Since the environment in which
a sound source is located affects sound pressure, unit
placement must be carefully evaluated. Sound power
levels for Stealth chillers are available on request.
Unit Isolation and Leveling
For additional reduction of sound and vibration, install
the optional elastomeric isolators.
Construct an isolated concrete pad for the unit or
provide concrete footings at the unit mounting points.
Mount the unit directly to the concrete pads or
footings.