16
AC-SVX002C-EN
Service Clearance
Figure 1. Unit service clearance requirements
36” (914.4mm)
40”
(1016
mm)
24”
(600.1mm)
Control
Panel
NO OBSTRUCTIONS ABOVE UNIT
TOP VIEW
See
note 1
83” (2108mm)
See note 2
N
No
otte
ess::
1. A full 40” clearance is required in front of the control panel. Must be measured from front of panel, not end
of unit base.
2. Clearance of 85” on the side of the unit is required for coil replacement. Preferred side for coil replacement is
shown (left side of the unit, as facing control panel), however either side is acceptable.
Weights
Table 3. Unit weights
Unit Size
(tons)
Standard Unit
Options - Additional Weight
Shipping
Operating
Pump Package
lb
kg
lb
kg
lb
kg
140
7754
3517
7896
3581
2970
1347
160
7754
3517
7896
3581
2970
1347
180
9434
4278
9576
4343
3205
1454
200
9434
4278
9576
4343
3205
1454
215
10376
4706
10519
4771
3711
1683
230
10523
4772
10700
4853
3711
1683
Note:
Weights include factory charge of refrigerant and oil.