Specifications
23
Electrical System
R-134a Circuit Compressor Motor:
Type
Semi-hermetic Reciprocating
Voltage
460/380V, 60/50 Hz, 3 Phase
Kilowatts (60 Hz)
5.60 kW
Horsepower (60 Hz)
7.5 hp
RPM (60 Hz)
1750 rpm
Full Load Amps
15.5 amps — 460V; 15.5 amps — 380V
Locked Rotor Amps (60 Hz)
83 amps — 460V; 82 to 91 amps — 380V
R-23 Circuit Compressor Motor:
Type
Hermetic Scroll
Voltage
460/380V, 60/50 Hz, 3 Phase
Kilowatts (60 Hz)
4.48 kW
Horsepower (60 Hz)
6.0 hp
RPM (60 Hz)
3550 rpm
Full Load Amps (60 Hz)
11 amps — 460V
Locked Rotor Amps (60 Hz)
70 amps — 460V
Condenser Fan Motor:
Type
460/380V, 60/50 Hz, 3 Phase
460/380V, 60/50 Hz
Kilowatts (60 Hz)
1.5 kW
749 Watts
Horsepower (60 Hz)
2.0 hp
0.75 hp
RPM (60 Hz)
1725 rpm
1725 rpm
Full Load Amps (60 Hz)
3.1 amps — 460V
1.25 amps
Locked Rotor Amps (60 Hz)
25 amps — 460V
35.7 amps
Evaporator Fan Motors*:
Type
460/380V, 60/50 Hz, 3 Phase
Number
3
Kilowatts (60 Hz) (Each)
0.75 kW
Horsepower (60 Hz) (Each)
1.0 hp
RPM (60 Hz) (Each)
3450 rpm, High Speed
1725 rpm, Low Speed*
Full Load Amps (60 Hz) (Each)
1.4 amps — 460V, High Speed
0.5 amps — 460V, Low Speed
Locked Rotor Amps (60 Hz)
10.3 amps — 460V, High Speed*
2.9 amps — 460V, Low Speed*
Electric Resistance Heater Rods:
Type
460/380V, 60/50 Hz, 3 Phase
Number
12
Watts (60 Hz) (Each)
680 Watts
Current Draw (Amps)
10 amps nominal (total) across each phase at the heater
contactor
Control Circuit Voltage:
29 Vac @ 60 Hz; 24 Vac @ 50 Hz
Evaporator Overheat Switch:
Opens
54 ±3 C (130 ±5 F)
Closes
38 ±4C (100 ±8 F)
*CRR DF applications operates the two-speed evaporator fan motors continuously on low speed. Evaporator fans stop during
defrost.
Summary of Contents for Thermo King CRR DF MPC2000
Page 5: ...4 ...
Page 11: ...List of Figures 10 ...
Page 13: ...Introduction 12 ...
Page 19: ...Safety Precautions 18 ...
Page 21: ...Service Guide 20 ...
Page 47: ...Unit Description 46 ...
Page 97: ...Microprocessor Controller 96 ...
Page 101: ...Electrical Maintenance 100 ...
Page 141: ...Structural Accessory Maintenance 140 ...
Page 147: ...Refrigeration System Diagnosis 146 ...
Page 150: ...149 CRR DF MPC2000 Controller Diagram ...
Page 151: ...150 CRR DF MPC2000 Main Relay Board Electrical Diagram ...
Page 152: ...151 CRR DF MPC2000 Unit Wiring Schematic Low Speed Winding ...
Page 153: ...152 CRR DF MP3000A Controller Diagram ...
Page 154: ...153 CRR DF MP3000A Main Relay Board Electrical Diagram ...
Page 155: ...154 CRR DF MP3000A Unit Wiring Schematic Low Speed Winding ...
Page 157: ...156 CRR DF Refrigeration System Components Page 2 of 2 ...
Page 161: ...160 CRR DF Full Cool Flow and Pressure Diagram Page 2 of 2 ...
Page 163: ...162 CRR DR Evacuation Station and Unit Connections Page 2 of 2 ...