TAM7-SF-2E-EN
21
SUBCOOLING ADJUSTMENT
System Matched with:
Indoor Unit Model No.
Outdoor Unit Model No.
Subcooling
Single compressor, 2 Stage HP
TAM7A0B30H21SD
TAM7A0B30H21EA
4A6H6024E/G, 4TWX6024E/G,
4A6H7024, 4TWX8024
9
˚
TAM7A0C36H21SD
TAM7A0C36H21EA
4A6H6036E/G, 4TWX6036E/G,
4A6H7036, 4TWX8036
10
˚
TAM7A0C48H21SD
TAM7A0C48H21EA
4A6H6048E/G, 4TWX6048E/G,
4A6H7048, 4TWX8048
8
˚
Single compressor, 2 Stage AC
TAM7A0B30H21SD
TAM7A0B30H21EA
4A7A6024E/G, 4TTX6024E/G,
4A7A7024, 4TTX8024
8
˚
TAM7A0C36H21SD
TAM7A0C36H21EA
4A7A6036E/G, 4TTX6036E/G,
4A7A7036, 4TTX8036
8
˚
TAM7A0C48H21SD
TAM7A0C48H21EA
4A7A6048E/G, 4TTX6048E/G,
4A7A7048, 4TTX8048
8
˚
Two compressor, 2 Stage HP
TAM7A0B30H21SD
TAM7A0B30H21EA
4A6Z0024A, 4TWZ0024A
9
˚
TAM7A0C36H21SD
TAM7A0C36H21EA
4A6Z0036A/B, 4TWZ0036A/B
10
˚
TAM7A0C48H21SD
TAM7A0C48H21EA
4A6Z0048A/B, 4TWZ0048A/B
12
˚
TAM7B0C60H51SC
TAM7B0C60H51EA
4A6Z0060A, 4TWZ0060A
12
˚
Two compressor, 2 Stage AC
TAM7A0B30H21SD
TAM7A0B30H21EA
4A7Z0024A, 4TTZ0024A
9
˚
TAM7A0C36H21SD
TAM7A0C36H21EA
4A7Z0036A/B, 4TTZ0036A/B
11
˚
TAM7A0C48H21SD
TAM7A0C48H21EA
4A7Z0048A/B, 4TTZ0048A/B
13
˚
NOTES:
1. Variable Speed outdoor units must be charged per the outdoor unit instructions.
2. All other matches must be charged per the nameplate charging instructions.
DISTANCE FROM BELLY BAND
TO SHAFT FACE OF MOTOR FOR
MINIMUM VIBRATION
WHEEL
BLOWER HOUSING
MOTOR
A
“A” is determined per chart
Wheel is centered in
Blower Housing
BELLY BAND
MODEL
DIM “ A “
TAM7A0A24H21SD
TAM7A0A24H21EA
TAM8C0A24V21CB
TAM8C0A24V21EA
2–3/8
TAM7A0B30H21SD
TAM7A0B30H21EA
TAM8C0B30V21CB
TAM8C0B30V21EA
2–3/8
TAM7A0C36H31SD
TAM7A0C36H31EA
TAM8C0C36V31CB
TAM8C0C36V31EA
2–3/8
TAM7A0C42H31SD
TAM7A0C42H31EA
TAM8C0C42V31CB
TAM8C0C42V31EA
2–3/8
TAM7A0C48H41SD
TAM7A0C48H41EA
TAM8C0C48V41CB
TAM8C0C48V41EA
2–3/8
TAM7B0C60H51SC
TAM7B0C60H51EA
TAM8C0C60V51CB
TAM8C0C60V51EA
2–3/8