52
RT-SVD03L-EN
Proper wiring configuration is required for correct unit
operation. Wiring harness plugs should be configured
as shown below for Voyager
™
units.
Figure 41.
Voyager
™
™
SZVAV configuration
36C E
To GTB
Figure 42.
Voyager
™
™
multi-speed configuration
Figure 43.
Voyager
™
™
standard configuration
Adjusting Maximum Unit Airflow -
Voyager
™
™
Light Commercial
Adjust the maximum airflow with sheaves and pulleys
as one would with a standard unit. Verify adjustments
in test mode in either maximum cooling (both
compressors running) or any stage of heat.
Field adjustment of the VFD is not necessary or
recommended with Voyager
™
multi-speed or SZVAV
package units.
Indoor Fan Control Description;
Odyssey
™
™
Multi-Speed and SZVAV VFD
Controlled Evaporator Fan Motor - Unit
Identification
Digits 9 and 10 of the TWE air handler identify the air
handler as standard constant volume, multi-speed or
SZVAV.
Fan type
Digits 9 and 10
Standard constant volume
00
Multi speed w/standard motor
03
Multi speed w/oversized motor
04
SZVAV w/standard motor
R3
SZVAV w/oversized motor
R4