RT-SVD03L-EN
51
Figure 37.
Precedent
™
™
7.5 to 10 tons multi-speed
configuration
Figure 38.
Precedent
™
™
7.5 to10 tons standard
configuration
Adjusting Maximum Unit Airflow
Adjust the R-136 potentiometer on the RTOM (same as
with 17 Plus) to change the potentiometer voltage (J-11
output) and thus change maximum fan speed. BC
Plenum fan units will output a 0-10 vdc signal from the
RTOM J-11. The potentiometer voltage chart is located
on a sticker on the fan housing itself and in the unit
Installation, Operations, and Maintenance manual
(IOM).
Indoor Fan Control Description;
Voyager
™
™
Multi Speed and SZVAV VFD
Controlled Evaporator Fan Motor - Unit
Identification
Voyager
™
units use a forward curved evaporator fan
with a VFD controlled motor for multi speed and
SZVAV options. Unit fan control type can be identified
by the 9th digit in the model number as described in
the following chart:
Fan type
Standard
Multi-
speed
SZVAV
No heat (TC*, WC*)
0 (zero)
A
F
Low heat
L
B
G
High heat
H
C
H
Mod heat
V
D
K
N
No
otte
e:: TCH241F4F0AB is a SZVAV unit without electric
heat.
Wiring and Configuration
Multi-speed units use two relays located in the control
box to switch speeds at the VFD.
Figure 39.
Multi-speed
Single zone VAV units use one relay and a vdc signal
from the J-11 of the RTOM to modulate the fan speed.
Figure 40.
Single zone VAV