RT-SVD03L-EN
41
•
J3-3 is modulating gas heat config. input J3-4 is
used with 27.5 to 50 ton units to configure
condenser fan control type.
•
J3-5 is used to configure the unit as a Voyager
™
Commercial unit. (27.5 to 50 ton units only).
Input is also used on 25 ton high efficiency Voyager
™
Light Commercial products to indicate 4 stages of
cooling are required.
J4 Output
The Precedent
™
6-10 Tons High Efficiency Heat Pump
units utilize a J4 output for compressor staging.
J4 Input
D
Diisscch
ha
arrg
ge
e a
aiirr sse
en
nsso
orr (10K @ 77°F/25°C) allows supply
air tempering, also discharge air information for
Building Automation systems (BAS) using COMM5
such as Tracer
®
Summit V13 and Tracker
®
Version 10.
Earlier versions of Tracker
®
(V6.5 and below) and any
Tracer
®
system using COMM3 or COMM4 do not
recognize this input.
The input seen by Tracer
®
(using COMM3 or COMM4)
and Tracker
®
(prior to Version 10) is “Supply Air
Temperature”, which is actually the Mixed Air
Temperature input from the ECA to the RTRM. The
other inputs on J4 are not used.
J5 Output
J5 is the 2-10 VDC output used when the unit has
modulating gas heat.
J6 Inputs
V
Ve
en
nttiilla
attiio
on
n o
ov
ve
errrriid
de
e inputs J6-1, 2, 3 are explained in
the application section of this manual.
J7 Inputs
•
F
Frro
osstta
att
™
™
3 to 25 tons
Closes 10F ±2º
Opens 50F ±2º
27.5 to 50 tons
Closes 30F ±2º
Opens 40F ±2º
When the Frostat
™
opens, the compressors will re-
start. There is no diagnostic during Frostat trip.
•
C
Cllo
og
gg
ge
ed
d ffiilltte
err ssw
wiittcch
h is factory set to close at
0.45”, however is adjustable from 0.05” to 12.0”. A
7/32” allen wrench is required for this adjustment.
When the switch is closed for 2 minutes, the service
indicator on the ZSM will be on (see diagnostics
section for details). When the switch opens, the
indicator is off (auto reset).
•
F
Fa
an
n p
prro
ov
viin
ng
g ssw
wiittcch
h ((3
3 tto
o 2
25
5 tto
on
nss)) is factory set to
open at 0.07”, and is adjustable from 0.05” to 12.0”,
though adjustment is not recommended. If the
switch does not open within 40 seconds after the
fan starts, the unit stops, requiring manual reset
from the zone sensor or BAS system, or by
resetting power to the unit. The SERVICE indicator
on the ZSM will pulse during fan fail mode.
•
F
Fa
an
n p
prro
ov
viin
ng
g ssw
wiittcch
h ((2
27
7..5
5 –– 5
50
0 tto
on
nss)) is factory set
to close at 0.15”, and is adjustable from 0.05” to
12.0”, though adjustment is not recommended. If
the switch does not close within 40 seconds after
the fan starts, the unit stops, requiring manual reset
from the zone sensor or BAS system, or by
resetting power to the unit. The SERVICE indicator
on the ZSM will pulse during fan fail mode.
•
S
Sm
mo
okke
e d
de
ette
ecctto
orr contacts are open during normal
operation. When closed, the unit shuts down
immediately. When the contacts are re-opened, the
unit will automatically restart.
N
No
otte
e:: Ventilation override option will override
smoke detector input through the RTOM.
J8 Input
DACR potentiometer for SZVAV use or configuration
jumper for multi speed use. R
Re
ella
attiiv
ve
e h
hu
um
miid
diitty
y sse
en
nsso
orr
provides input to reheat for dehumidification.
J9 Input
R
Re
eh
he
ea
att e
en
na
ab
blle
e iin
np
pu
utt provides a binary input to
configure the unit for reheat.
J10 Input
H
Hu
um
miid
diisstta
att provides binary input to energize the
reheat valve for dehumidification. When the humidistat
is satisfied, the reheat valve is de-energized (3–25 ton
units only).
J11 Output
F
Fa
an
n cco
on
nttrro
oll o
ou
uttp
pu
utt for Multi-speed and SZVAV.
J12 Input
H
He
ea
att p
pu
um
mp
p llo
ow
w a
am
mb
biie
en
ntt lliim
miitt cco
on
nffiig
g provides a
configuration input to disable compressor heating on
heat pumps when the outdoor temperature falls below
1.4°F. Compressor Heating is re-enabled when the
Outdoor Temperature rises to 3.5°F.
P
Prre
ecce
ed
de
en
ntt
™
™
H
Hiig
gh
h E
Effffiicciie
en
nccy
y H
He
ea
att P
Pu
um
mp
pss llo
ow
w
a
am
mb
biie
en
ntt lliim
miitt provides a configuration input to disable
compressor heating on heat pumps when the outdoor
temperature falls below 30°F. It is user adjustable with
a BAS or a TD5.
A
Alla
arrm
m iin
nd
diicca
attiio
on
n cco
on
nffiig
g provides a configuration
input to determine which diagnostics will energize the
Alarm Indication output. If Open, the Alarm Indication
output will energize whenever the RTRM System LED is
blinking a 2-blink error code. If Closed to common, the
Alarm Indication output will energize whenever any key
system component is locked out (Cooling, Heating,
etc.).