The RTOM gets power from and communicates with
the RTRM.
Any of these optional ReliaTel
™
devices require the
use of an RTOM:
•
Condensate overflow switch (COS)
•
Clogged filter switch (CFS)
•
Discharge air sensor (DAS) used for supply air
tempering and ICS input data
•
Fan failure switch (FFS)
•
Factory-installed smoke detector
N
No
otte
e:: A factory-installed smoke detector provides
instant shutdown and ICS alarm output.
•
Frostat
™
(FOS)
ReliaTel
™
™
Ventilation Module (RTVM) —
27.5 to 50 Tons Units
The RTVM is a module required for units configured
with space pressure control with Statitrac
™
. The
module controls the exhaust damper position 0-10Vdc
output as well as the space pressure sensor calibration
routine. The module accepts the following inputs:
•
Statitrac
™
configuration
•
Space pressure input
•
Space pressure setpoint
•
Space pressure setpoint deadband
•
Traq
™
(Voyager
™
Commercial 27.5 to 50 tons)
ReliaTel
™
™
Ventilation Module (RTVM) —
3 to 25 Tons Units
The RTVM is a module for Demand Control Ventilation
(DCV) on multi-speed and Single-Zone Variable Air
Volume (SZVAV) units.
ReliaTel
™
™
Dehumidification Module
(RTDM)
N
No
otte
e:: Available on 27.5 to 50 Tons units only.
The RTDM is a module required for units configured
with modulating dehumidification. The module
controls modulating cooling and reheat valves as well
as the reheat circuit pumpout solenoid. The module
accepts the following inputs:
•
Reheat circuit entering evaporator temperature
•
Reheat circuit low pressure cutout input
Economizer Actuator with Module (ECA
or RTEM)
The economizer can be used with or without the
options module. The actuator has a detachable
communicating module, which can be replaced
separately. The outdoor air sensor, connected to the
RTRM, provides outdoor temperature information for
the changeover decision.
The ECA accepts the following inputs:
•
Mixed air sensor (MAS)
•
Return air sensor (RAS) for comparative enthalpy or
ICS input data
•
Outdoor humidity sensor (OHS) for reference or
comparative enthalpy
•
Return air humidity sensor (RHS) for comparative
enthalpy
•
CO
2
sensor 0-10 VDC input (DCV)
•
Remote minimum potentiometer (RMP)
•
Active/passive DCV configuration input (RTEM only)
•
The power exhaust relay is connected to the ECA
module
ReliaTel
™
™
Electromechanical
Economizer Module (RTEM-EM)
•
The RTEM-EM is an economizer module configured
to support electro-mechanical HVAC units. The
module will require 24Vac input power and provide
control for an outdoor air damper actuator. The
module features 6 pots on for potentiometers
onboard. The potentiometers control building
design and demand control ventilation (DCV)
minimum damper positions, DCV and CO
2
setpoints and limits, and dry bulb and enthalpy
settings. The module supports the following inputs:
•
Return air temperature sensor (RAS)
•
Outside air temperature sensor (OAS)
•
Mixed air temperature sensor (MAS)
•
Return air humidity sensor (RHS) for comparative
enthalpy
•
Outside air humidity sensor (OHS) for comparative
enthalpy
•
CO
2
sensor 0-12VDC input (DCV)
•
Remote minimum position potentiometer
Variable Speed Module (VSM)
•
The VSM allows communication between
ReliaTel
™
controls platform and a variable speed
condenser fan (ECM) motor and variable speed
compressor drive for Precedent
™
and Voyager
™
light commercial products. The VSM controller is
applied to the following units:
•
Precedent
™
3 to 5 ton units to control a variable
speed condenser fan and variable speed
compressor drive
•
Voyager
™
light commercial 12.5 and 17.5 ton units
to control a variable speed condenser fan and
variable speed compressor drive