Ingersoll-Rand Nirvana IRN100-200H-2S Operation And Maintenance Manual Download Page 74

10.0  MAINTENANCE

IRN37–160K–CC  &  IRN50–200H–CC  &  IRN75–160K–2S  &  IRN100–200H–2S

71

CAUTION

Do not use any form of sealant on either the
separator tank or the separator tank cover faces.

Separator tank / Pressure system 

At 2000 hour intervals, inspect the external surfaces
of the airend and separator tank, including all fittings,
for visible signs of impact damage, excessive
corrosion and abrasions. When changing the
separator element inspect the internal components
and surfaces. Any suspect parts should be replaced
before the compressor is put back into service.

The separator tank should also be tested and
inspected in accordance with any national or local
codes that may exist.

Coolant hoses

S

The flexible hoses that carry coolant through the
cooling system may become brittle with age and
will require replacement. Have your local
Ingersoll–Rand Distributor or Air Center inspect
them every 3 months and replace them as needed
or every 2 years.

S

Depending on the location of the hose, it may
contain compressor coolant.  It is recommended to
drain the coolant into a clean container. Cover the
container to prevent contamination. If the coolant
is contaminated, a new charge of coolant must be
used.

S

Remove the hose.

S

Install the new hose and refill the unit with coolant.
Start the compressor, check for leaks and check
coolant level.  Refill as necessary

Pressure relief valve check

The pressure relief valve must be frequently tested
and regularly maintained. Remove from the machine
and check for the correct operating pressure. Adjust
as necessary. If operating conditions are particularly
severe, the frequency of testing and maintenance
must be increased accordingly. A pressure relief
valve check must also be performed at the end of
any non–service period. The user must establish the
frequency of such tests as it is influenced by such
factors as the severity of the operating environment.

CAUTION

High pressure air will discharge through the
discharge ports of the valve during pressure
relief valve check. Wear ample clothing, gloves,
safety glasses and ear protection during valve
testing.

Run the compressor for about 10 minutes by venting
air from the system to let the unit warm up.  With the
unit running, test at or near the maximum operating
pressure by opening the valve for the minimum
period required to flush the valve seat free of debris.
This can be accomplished by holding the test lever
fully open or unscrewing the spring pressure retaining
cap, depending on the type of valve installed.  If there
is no evidence of discharge or the valve does not fully
close, discontinue use of equipment and contact a
licensed contractor or qualified service personnel.

The pressure relief valve should also be tested and
re–calibrated in accordance with any national or local
codes that may exist.

 

If no code exists, IR

recommend that the pressure relief valve is
recalibrated at intervals of one year.

Air filter change procedure

S

Unclip the retaining cap and withdraw the old
element.

S

Fit the new element and refit the retaining cap.

Aircooled Cooler Cleaning 

Ensure that the compressor is isolated from the
compressed air system and is vented of all pressure.
When undertaking any work on the compressor
always use certified lifting equipment and employ
sound working principles.

Ensure that the main power disconnect switch is
locked off and tagged.

Visually check the outside of the cooler cores to be
certain that a complete cleaning of the cooler is
required. Frequently, dirt, dust or other foreign
material may only need to be removed with a vacuum
to remedy the problem.

When the cooler is covered with a combination of oil,
grease or other heavy substances that may affect the
unit’s cooling, then it is recommended that the cooler
cores be thoroughly cleaned on the outside.

If it is determined that the compressor operating
temperature is higher than normal due to the external
passages between the fins of the cooler cores being
restricted with deposits of foreign material, then the
cooler should be removed for cleaning.

N50/100H (N37/75K)

Following are instructions for tilting the cooler away
from the enclosure and cleaning of the cooler.

S

Remove 6 screws from lower rear fixed panel and
remove panel.

S

Remove 10 screws from the rear intake panel and
remove panel.

S

Loosen clamp and disconnect the air inlet hose
from the intake plenum.

S

Remove intake plenum. Note, plenum is
unsupported, before removing the 8 screws
from the intake plenum, block underside of
plenum prior to removing screws to prevent
plenum from falling.

Summary of Contents for Nirvana IRN100-200H-2S

Page 1: ...t and have read the Maintenance Manuals IRN37 160K CC IRN50 200H CC IRN75 160K 2S IRN100 200H 2S Ensure that the Operation and Maintenance manual is not removed permanently from the machine TM N37K N4...

Page 2: ...INGERSOLL RAND COMPANY LIMITED SWAN LANE HINDLEY GREEN WIGAN WN2 4EZ UNITED KINGDOM DECLARE THAT UNDER OUR SOLE RESPONSIBILITY FOR MANUFACTURE AND SUPPLY THE PRODUCT S IRN37K CC IRN45K CC IRN55K CC IR...

Page 3: ...ser or others without Company s prior written approval The effects of corrosion erosion and normal wear and tear are specifically excluded Performance warranties are limited to those specifically stat...

Page 4: ...atercooled units 7 6 Outdoor sheltered installation 8 0 GENERAL INFORMATION 27 8 1 Technical information 8 2 Installation drawing 8 3 Process and instrumentation diagram 8 4 Electrical schematic 8 5 G...

Page 5: ...ories pipes and connectors added to the compressed air system should be of good quality procured from a reputable manufacturer and wherever possible be of a type approved by Ingersoll Rand clearly rat...

Page 6: ...ersoll Rand cannot be held responsible for equipment in which non approved repair parts are installed WARNING The motor rotor contains a powerful magnetic field This field can effect the operation of...

Page 7: ...AR As required SM Sitemaster Sitepack HA High ambient machine WC Watercooled machine AC Aircooled machine ERS Energy recovery system T E F C Totally enclosed fan cooled motor IP54 O D P Open drip pro...

Page 8: ...mpany reserves the right to make changes or add improvements without notice and without incurring any obligation to make such changes or add such improvements to products sold previously No of units o...

Page 9: ...hat the canopy doors are closed during operation Installation of this compressor must be in accordance with recognized electrical codes and any local Health and Safety Codes Use only safety solvent fo...

Page 10: ...ient is unconscious or having convulsions The above information contains data supplied in support of United Kingdom Control of Substances Hazardous to Health C O S H H regulations Transport When loadi...

Page 11: ...ompatibility between discharge piping system accessories and software must be assured S For the foregoing reasons the use of plastic piping soldered copper fittings and rubber hose as discharge piping...

Page 12: ...eration and maintenance a minimum of 3 feet clearance on 3 sides is required 3 1 2 feet is required in front of the control panel or minimum required by latest National Electrical code or applicable l...

Page 13: ...a pressurized shutdown mode Relieve pressure before removing filter plugs caps fittings or covers 22061915 Rev A NOTICE Air discharge CAUTION Use of incorrect coolant can cause system contamination U...

Page 14: ...hereafter or when coolant is changed NOTICE Rotation Rotation Rotation WARNING HIGH VOLTAGE Do not attempt any work Read manual Trained service personnel only Remove electrical supply Wait 15 minutes...

Page 15: ...in satisfactory compressor operation and maintenance a minimum of 3 feet clearance on 3 sides is required 3 1 2 feet is required in front of the control panel or minimum required by latest National El...

Page 16: ...ns Warning WARNING Electrical shock risk WARNING Pressurized component or system WARNING Hot surface WARNING Pressure control WARNING Corrosion risk WARNING Air gas flow or Air discharge WARNING Press...

Page 17: ...rature below 0_C consult the Operation and Maintenance manual Read the Operation and Maintenance manual before operation or maintenance of this machine is undertaken Do not stack Do not operate the ma...

Page 18: ...rk lift truck from this side only Emergency stop Tie down point Lifting point On power Off power SET SEQUENCER STATUS LOAD SEQUENCER AUTOMATIC CONTROL COMPRESSOR OFF LOAD UNLOADED RESET COMPRESSOR STA...

Page 19: ...AIR DISCHARGE PRESSURIZED TANK ON OFF CYCLE COOLANT FILTER AIR FILTER ON OFF PUSH BUTTON COOLANT PRESSURE AIR PRESSURE STAR DELTA IEC 617 7 AUTOMATIC RESTART HEAT EXCHANGER MAINTENANCE MAINTENANCE PRO...

Page 20: ...50 200H CC IRN75 160K 2S IRN100 200H 2S BELT TENSION FILTER MOTOR LUBRICATION FRAGILE KEEP DRY THIS WAY UP USE NO HOOKS NO SIDE CLAMPS ROTATION POWER INLET AC WATER IN WATER OUT TRAINED SERVICE PERSON...

Page 21: ...ncealed damage notation If you give the transportation company a clear receipt for goods that have been damaged or lost in transit you do so at your own risk and expense WE AT lR ARE WILLING TO ASSIST...

Page 22: ...avy components during major overhaul Use only lifting points provided Minimum space in front of control panel door as required by National or Local codes must be maintained The compressor can be insta...

Page 23: ...nsure that downstream equipment is compatible When two rotary units are operated in parallel provide an isolation vaIve and drain trap for each compressor before the common receiver The built in after...

Page 24: ...fic applied voltage prior to starting A hole is provided for incoming power connection If it is necessary to make a hole in the control box in a different location care should be taken to not allow me...

Page 25: ...ltage spikes line notching harmonics or other power quality related problems will not be covered by the standard compressor warranty The correct type and rating of line input fuse MUST BE fitted onto...

Page 26: ...38 10 N55 19 5 27 7 1 45 11 9 N75 30 7 7 42 11 1 68 18 N90 34 9 0 45 11 9 77 20 3 N110 41 10 8 59 15 6 95 25 1 N132 64 16 9 82 21 7 123 32 5 N160 73 19 3 95 25 1 150 39 6 Water temperature and pressu...

Page 27: ...is dependent on temperature and pH The higher the pH value the greater the chance of scale formation Scale can be controlled with water treatment Corrosion In contrast to scale formation is the probl...

Page 28: ...er flow rate through the cooler may be several times the recommended maximum which will lead to rapid failure Sea Water Pressure Bar psi Orifice diameter in mm inch to give a maximum sea water flow of...

Page 29: ...160K CC IRN50 200H CC IRN75 160K 2S IRN100 200H 2S 7 6 OUTDOOR SHELTERED INSTALLATION Nirvana compressors are not suitable for outdoor installation Installing a Nirvana compressor outside voids the w...

Page 30: ...4 75 HAT switch setting _C _F 120 248 120 248 120 248 120 248 Performance Flow at 7 5 Barg m3 min 6 43 7 42 Flow at 8 5 Barg m3 min 6 17 7 07 Flow at 10 Barg m3 min 5 75 6 46 Flow at 100 psig cfm 235...

Page 31: ...kage full load current at 575V A 56 63 Max fuse size 220V 230V A 250 250 250 250 Max fuse size 380V 415V A 125 125 125 125 Max fuse size 440V 480V A 125 125 125 125 Max fuse size 550V 575V A 100 100 1...

Page 32: ..._F 120 248 120 248 120 248 120 248 Performance Flow at 7 5 Barg m3 min 10 18 13 51 Flow at 8 5 Barg m3 min 9 40 12 69 Flow at 10 Barg m3 min 8 51 11 67 Flow at 100 psig cfm 386 490 Flow at 125 psig cf...

Page 33: ...ackage full load current at 575V A 79 104 Max fuse size 220V 230V A 300 N A 300 N A Max fuse size 380V 415V A 150 200 150 200 Max fuse size 440V 480V A 150 200 150 200 Max fuse size 550V 575V A 125 15...

Page 34: ..._C _F 120 248 120 248 120 248 120 248 Performance Flow at 7 5 Barg m3 min 17 1 20 0 Flow at 8 5 Barg m3 min 15 3 19 2 Flow at 10 Barg m3 min 14 0 17 5 Flow at 100 psig cfm 655 739 Flow at 125 psig cfm...

Page 35: ...ent at 460V A 167 197 Mean package full load current at 575V A 134 158 Max fuse size 380V 415V A 250 350 Max fuse size 440V 480V A 200 250 Max fuse size 550V 575V A 200 200 Fuse type Fast acting class...

Page 36: ...20 248 120 248 120 248 Performance Flow at 7 5 Barg m3 min 23 5 28 0 Flow at 8 5 Barg m3 min 22 3 26 0 Flow at 10 Barg m3 min 21 0 25 0 Flow at 100 psig cfm 993 Flow at 125 psig cfm 892 Flow at 140 ps...

Page 37: ...t 460V A 256 Mean package full load current at 575V A 205 Max fuse size 380V 415V A 300 400 Max fuse size 440V 480V A 350 Max fuse size 550V 575V A 350 Fuse type Fast acting class J T or semiconductor...

Page 38: ...20 248 120 248 120 248 120 248 120 248 120 248 Performance Flow at 7 5 Barg m3 min 15 7 18 0 22 1 Flow at 8 5 Barg m3 min 14 2 17 5 20 4 Flow at 10 Barg m3 min 13 1 15 4 18 9 Flow at 14 Barg m3 min 12...

Page 39: ...package full load current at 460V A 136 167 197 Mean package full load current at 575V A 108 134 158 Max fuse size 380V 415V A 250 250 350 Max fuse size 440V 480V A 200 250 250 Max fuse size 550V 575V...

Page 40: ...mance Flow at 7 5 Barg m3 min 26 2 31 1 Flow at 8 5 Barg m3 min 24 2 29 6 Flow at 10 Barg m3 min 23 1 27 2 Flow at 14 Barg m3 min 18 4 22 2 Flow at 100 psig cfm 1100 Flow at 125 psig cfm 990 Flow at 1...

Page 41: ...t 460V A 256 Mean package full load current at 575V A 205 Max fuse size 380V 415V A 300 400 Max fuse size 440V 480V A 350 Max fuse size 550V 575V A 350 Fuse type Fast acting class J T or semiconductor...

Page 42: ...4 NPT Female Note Pipe condensate drain lines separately to an open drain due to differences in drain pressures Read operations manual and check local regulations D Cooling airflow E Exhaust airflow F...

Page 43: ...ectrical inlet C 1 4 NPT Female Note Pipe condensate drain lines separately to an open drain due to differences in drain pressures Read operations manual and check local regulations D Cooling airflow...

Page 44: ...8 0 GENERAL INFORMATION IRN37 160K CC IRN50 200H CC IRN75 160K 2S IRN100 200H 2S 41 8 2 INSTALLATION DRAWING N90 160K N125 200H SINGLE STAGE N75 160K N100 200H TWO STAGE...

Page 45: ...K units B 63mm 2 48 Electrical inlet C 1 4 NPT Female Note Pipe condensate drain lines separately to an open drain due to differences in drain pressures Read operations manual and check local regulati...

Page 46: ...8 0 GENERAL INFORMATION IRN37 160K CC IRN50 200H CC IRN75 160K 2S IRN100 200H 2S 43 8 3 PROCESS AND INSTRUMENTATION DIAGRAM N37 75K CC N50 100 CC...

Page 47: ...solenoid valve 23 Drive motor 24 Blower motor 25 Cooling air blower 26 Cooling water inlet W C only 27 Cooling water outlet W C only 28 Pressure transducer 3APT 29 Pressure transducer 6APT 30 Dryer c...

Page 48: ...ERAL INFORMATION IRN37 160K CC IRN50 200H CC IRN75 160K 2S IRN100 200H 2S 45 8 3 PROCESS AND INSTRUMENTATION DIAGRAM N90 160K N125 200H SINGLE STAGE AND N75 160K N100 200H TWO STAGE Revision B 10 02 2...

Page 49: ...ooling water outlet W C only 28 Pressure transducer 3APT 29 Pressure transducer 6APT 30 Dryer customer supply equipment 31 Line filters customer equipment 32 Receivers customer equipment 33 Dryer AUX...

Page 50: ...8 0 GENERAL INFORMATION IRN37 160K CC IRN50 200H CC IRN75 160K 2S IRN100 200H 2S 47 8 4 ELECTRICAL SCHEMATIC N37K N75K N50H N100K...

Page 51: ...heater 25 watts K1 Relay run K2 Relay fault KM1 Contactor main motor KM4 Contactor blower motor MCB1 Breaker miniature circuit transformer MCB2 Breaker miniature circuit VFD MCB3 Breaker miniature ci...

Page 52: ...8 0 GENERAL INFORMATION IRN37 160K CC IRN50 200H CC IRN75 160K 2S IRN100 200H 2S 49 8 4 ELECTRICAL SCHEMATIC N75K N160K N100H N200H N75H N160H Revision H 12 02 22093058...

Page 53: ...S Switch emergency stop EXC External communications FD Fan drive FM Motor Blower GND Ground HB Heatsink blower HTRI Heater 125 watts K1 Relay run K2 Relay fault KM1 Contactor main motor KM5 Contactor...

Page 54: ...and drain The coolant system consists of a sump cooler thermostatic valve anti condensation valve and a filter When the unit is operating coolant is forced by air pressure from the separator tank to...

Page 55: ...ove Check that the coolant level is at least visible in the center of the sight glass add coolant if necessary Refer to maintenance procedures for setting correct level Ensure that the discharge air i...

Page 56: ...s However if the compressor stops for this reason it will automatically restart when the system pressure falls below the target pressure Blowdown mode If the blowdown mode is set to on the compressor...

Page 57: ...ence 4 F1 Not used 5 F2 Not used 6 Arrows These up and down buttons have multiple functions relating to the right half of the display screen When lists are presented the buttons are used to move up or...

Page 58: ...n by pressing the arrow buttons to the right of the screen The small arrow s displayed in the upper right corner of the screen indicate when you can move up and or down through a list The arrow button...

Page 59: ...re 5 Airend Discharge Temperature 6 Injected Coolant Temperature 7 Inlet Temperature 7 Sump Pressure 8 Separator Pressure Drop 9 Interstage Pressure 9 Coolant Filter 10 Inlet Filter 11 Total Hours 12...

Page 60: ...ATUS button is pressed The language and units of measure are pre set prior to the compressor leaving the factory MAIN MENU 100 OPERATOR SETPOINTS OPTIONS READY TO START SENSOR CALIBRATION ALARM HISTOR...

Page 61: ...set Date Service menu 1 1 25535 1 A setpoint s value can be changed by first highlighting the item and its value and pressing the SELECT button to highlight just the value When the value line is highl...

Page 62: ...If this mode is selected to ON the compressor will open the blowdown valve anytime that it stops This will vent pressure from the airend and the separator tank If this mode is selected to OFF the blo...

Page 63: ...sure measured by this sensor is shown in the CURRENT STATUS display as the Remote Pressure reading The local sensor at the package discharge is still used for Immediate Stop for certain Alarm conditio...

Page 64: ...BRATION Pressure sensor calibration is done through the SENSOR CALIBRATION screen Sensor calibration can only take place when the machine is stopped Calibration needs to be done only after a sensor ha...

Page 65: ...the list up and down using the arrow buttons Pressing the ALARM HIST button will return the display to the ALARM HISTORY screen Alarm histories can be exited by pressing either the STATUS or MAIN MEN...

Page 66: ...that number by the motor kW per hour for that size of compressor at 100 capacity AVERAGE CAPACITY Displays the compressor s average capacity in cfm or m3 for the time period that was started by select...

Page 67: ...he unit is under the control of an external device such as an ISC and the discharge pressure is greater than the immediate stop pressure AUXILIARY WARNING 1 or 2 Will occur if the auxiliary warning in...

Page 68: ...ay the number of the fault condition CONTROL POWER LOSS This will occur if the control circuit is broken by a bad connection or safety switch e g HAT Switch Phase Monitor Any fall of voltage below 100...

Page 69: ...vel selected Refer to operating instructions The customer can only reset the warning for 24 hours by pressing the set button IR service engineers will master reset the warning after completing the ser...

Page 70: ...18000 Daily Coolant filter Change Change Change Change Air filter Check pressure Change Change Separator element Check pressure Change Change ULTRA COOLANT Check Sample Sample Change Power Drive Modul...

Page 71: ...TION When using any form of liquid for cleaning ensure that all electrical components are protected or covered to prevent ingress of liquid WARNING This compressor contains a variable frequency drive...

Page 72: ...c S appropriate personal protective equipment is worn S loose clothing jewelry long hair etc is made safe S warning signs indicating that Maintenance Work is in Progress are posted in a position that...

Page 73: ...Clean the mating face of the housing S Remove the new Ingersoll Rand replacement element from its protective package S Apply a small amount of coolant to the element seal S Screw the new element down...

Page 74: ...et the unit warm up With the unit running test at or near the maximum operating pressure by opening the valve for the minimum period required to flush the valve seat free of debris This can be accompl...

Page 75: ...cooling plenum and remove covers S Cover main drive motor PDM Heat sink blower motor drain valve and cooling motor variable speed drive with plastic sheeting to prevent damage from entrance of cleani...

Page 76: ...or tank scavenge check valve orifice S Disconnect tubing at each end of check valve screen orifice assembly S Check orifice and clean if required Use suitable tool and remove orifice from its housing...

Page 77: ...detergent solution S Replace any defective parts see parts manual for repair kit S Re assemble and later with machine running check that condensate is expelled at regular period and no alarms are sig...

Page 78: ...Check supply is switched on If so contact a qualified electrician Intellisys controller failure Check supply to unit Replace unit Starter failure Isolate supply lock off and tag Replace failed compone...

Page 79: ...your local IR representative Motor speed too low caused by fault in drive settings See section on drive faults Intellysis controller fault Overhaul or replace Drive motor fault See section on drive fa...

Page 80: ...essive Panels or doors are not closed properly Rectify fault noise Air leaks from internal pipework components Overhaul or replace Blower or blower motor bearings worn Overhaul or replace Loose debris...

Page 81: ...replace consumption See also discharge air is contaminated with coolant See above 11 2 INTELLISYS FAULTS INDICATED ON THE INTELLISYS CONTROLLER FAULT CAUSE REMEDY Emergency Stop Emergency stop button...

Page 82: ...oller has tripped the compressor A fault has occurred Repair fault reset Intellisys controller Invalid Calibration Calibration done with pressure in compressor Depressurise and re calibrate with press...

Page 83: ...s VSD fault 0 VSD fault 1 etc The following VSD faults may be investigated and remedied at source For all other VSD faults contact your local IR customer support representative FAULT CAUSE ACTION VSD...

Page 84: ......

Page 85: ......

Reviews: