8.0 GENERAL INFORMATION
IRN37–160K–CC & IRN50–200H–CC & IRN75–160K–2S & IRN100–200H–2S
38
N132K
N160K
N200H
Water Cooling System
Cooling (clean) water flow m
3
/min (US
gallon/min) @ 10
_
C (50
_
F) / 32
_
C (90
_
F)
4.75 / 10.56
(18 / 40)
4.75 / 10.56
(18 / 40)
4.75 / 10.56
(18 / 40)
Maximum
∆
P in air ducts Pa (inch WG)
62 (0.25)
62 (0.25)
62 (0.25)
Compressed air outlet
∆
T
_
C (
_
F)
14 (25)
14 (25)
14 (25)
Main Power Circuit
***
Mean package full load current at 400V(A)
261
314
Mean package full load current at 460V(A)
–
–
256
Mean package full load current at 575V(A)
–
–
205
Max fuse size @ 380V – 415V (A)
300
400
–
Max fuse size @ 440V – 480V (A)
–
–
350
Max fuse size @ 550V – 575V (A)
–
–
350
Fuse type
Fast acting class J, T or semiconductor type, current limiting
interrupt rating 200, 000 Amps
RMS SYM.
Heater Circuit
110V Single Phase Rating (A)
4
4
4
230V Single Phase Rating (A)
4
4
4
Fuse type
General purpose
* In accordance with PNEUROP PN8NTC2.3
** Tolerances in accordance with ISO 1217
*** Always apply local electrical codes for sizing cables and fusing. In the abscence of local codes the minimum
cable size should be calculated on basis of mean package full load current X1.25 (i.e. 25% margin)