8.0 GENERAL INFORMATION
IRN37–160K–CC & IRN50–200H–CC & IRN75–160K–2S & IRN100–200H–2S
33
N132K
N160K
N200H
General
Sound pressure level dB(A) *
75
75
75
Maximum ambient temperature
_
C (
_
F)
46 (115)
46 (115)
46 (115)
Minimum ambient temperature
_
C (
_
F)
1.7 (35)
1.7 (35)
1.7 (35)
Weight Kg (lbs)
3175 (6985)
3175 (6985)
3175 (6985)
Maximum pressure barg (psig)
10 (145)
10 (145)
10 (145)
Minimum pressure barg (psig)
4.5 (65)
4.5 (65)
4.5 (65)
Coolant capacity litres (US gal)
90 (24)
90 (24)
90 (24)
HAT switch setting
_
C (
_
F)
120 (248)
120 (248)
120 (248)
Performance
**
Flow at 7.5 Barg (m
3
/min)
23.5
28.0
–
Flow at 8.5 Barg (m
3
/min)
22.3
26.0
–
Flow at 10 Barg (m
3
/min)
21.0
25.0
–
Flow at 100 psig (cfm)
–
–
993
Flow at 125 psig (cfm)
–
–
892
Flow at 140 psig (cfm)
–
–
812
Air Cooling System
Cooling air flow m
3
/min (cfm)
382 (13500)
382 (13500)
382 (13500)
Maximum
∆
P in air ducts Pa (inch WG)
124 (0.5)
124 (0.5)
124 (0.5)
Compressed air outlet
∆
T
_
C (
_
F)
8 (15)
8 (15)
8 (15)
* In accordance with PNEUROP PN8NTC2.3
** Tolerances in accordance with ISO 1217
*** Always apply local electrical codes for sizing cables and fusing. In the abscence of local codes the minimum
cable size should be calculated on basis of mean package full load current X1.25 (i.e. 25% margin)