Operation & Maintenance Manual
Options
98
Low Ambient Option Operation
When the ambient temperature falls to the point that the aftercooler outlet temperature is
approaching 45°F (7°C), the Temperature Control Unit (TCU), mounted on the rear of the
control panel, will automatically adjust the louvers to control the cooling airflow through the
aftercooler.
In the event that the unit is operating under abnormal conditions (i.e., an enclosure door open)
which would cause excessive cooling of the aftercooler, a temperature sensor in the
aftercooler outlet header will signal the TCU to further close the louvers if the compressed air
temperature falls to approximately 36°F (2°C) or lower.
There are no user selectable or serviceable components in the TCU. Contact Ingersoll–Rand
Service if any abnormal operation of the freeze protection control system occurs.
Maintenance
Daily Maintenance:
Verify, during full–load (maximum compressed air delivery) that the IQ System filter restriction
indicators do not show excessive restriction. Restriction indicators for the filters are mounted
inside the control panel, and will shut down the compressor if restriction exceeds
recommended values.
Weekly Maintenance:
•
Remove Y–strainer screens at the bottom of the moisture separator and both filters
and clean out any residue.
•
Verify that the orifices below the Y–strainers are not clogged.
•
Verify that the piping from the orifice purge points to the exhaust system is not
clogged.
Yearly Maintenance:
The normal maintenance interval on the primary and secondary IQ System filters is one year,
or earlier if pressure drop becomes excessive. Restriction indicators for the filters are mounted
on the filter support inside the front door, and will shut down the compressor if restriction
exceeds recommended values.
Filter Replacement
•
With engine stopped, ensure pressure is relieved from air system.
•
Remove all wires and hoses connected to drains on bottom of each filter housing.
Inspect fittings and hoses for any blockage. Clean if necessary.
•
Using a chain wrench or similar tool, loosen the housing. The housing should be
removed by hand after loosening, taking care to prevent the housing from falling to
the floor panel.
•
Lower the housing to floor panel and lean it against the airend. Remove and replace
the filter element, being careful not to damage outer wrap.
Summary of Contents for MHP825WCAT
Page 7: ...5 Foreword...
Page 10: ...8 Always use Ingersoll Rand Replacement parts...
Page 11: ...9 Warranty...
Page 18: ...Operation Maintenance Manual Warranty 16...
Page 19: ...17 Noise Emission...
Page 24: ...22 Always use Ingersoll Rand Replacement parts...
Page 25: ...23 Safety Symbols...
Page 27: ...Safety Symbols Operation Maintenance Manual 25...
Page 28: ...Operation Maintenance Manual Safety Symbols 26...
Page 29: ...Safety Symbols Operation Maintenance Manual 27...
Page 32: ...30 Always use Ingersoll Rand Replacement parts...
Page 33: ...31 General Information MSA SRG HRG...
Page 35: ...General Information MSA SRG HRG Operation Maintenance Manual 33...
Page 39: ...37 Operating Instructions...
Page 43: ...Operating Instructions Operation Maintenance Manual 41...
Page 57: ...55 Maintenance...
Page 78: ...Operation Maintenance Manual Maintenance 76 Torque Values...
Page 82: ...80 Always use Ingersoll Rand Replacement parts...
Page 83: ...81 Machine Systems...
Page 84: ...Operation Maintenance Manual Machine Systems 82 Machine Systems Control System Schematic...
Page 91: ...89 Fault Finding...
Page 96: ...94 Always use Ingersoll Rand Replacement parts...
Page 97: ...95 Options...
Page 102: ...100 Always use Ingersoll Rand Replacement parts...
Page 103: ...101 Parts Ordering...
Page 108: ...106 Always use Ingersoll Rand Replacement parts...
Page 109: ...2004 Ingersoll Rand Company Printed in the USA...