Ingersoll-Rand D127NC Operator'S Manual Download Page 6

Nirvana Cycling Refrigerated Dryer 75 through 150 scfm

http://air.irco.com

5

7.1 INTRODUCTION

Ingersoll Rand Nirvana Cycling dryers remove moisture from
compressed air by cooling the air temperature to between 34° and 38°F
(1 and 3°C). This causes vapors to condense into liquid droplets which
can then be easily removed from the air. The major systems of the dryer
which contribute to its operation are the Air System, the Moisture
Removal System, the Refrigeration System, the Thermal Mass
Circulating System and the Controls. The following paragraphs describe
each of the systems in greater detail.

7.2 AIR SYSTEM

The air system consists of the dryer components which are in contact
with the compressed air. Referring to Figure 1 and following the bold “

AIR

7.0 PRINCIPLES OF OPERATION

FLOW

,” hot saturated air from the compressor enters the

precooler/reheater where the air temperature is reduced prior to
entering the chiller by the cool air exiting the air/moisture separator. This
precooling allows for the use of a smaller refrigeration system. The air
then goes into the chiller section where it is further cooled to the desired
dew point by a thermal mass fluid. The temperature of the thermal mass
fluid is maintained by the refrigeration circuit and controls. The air
continues to the separator where moisture is removed, thereby, allowing
the cool, dry air to return back to the precooler/reheater to be heated by
the incoming moist hot air. The air exiting the “reheater” portion of the
dryer should be approximately 15°- 20°F lower than the inlet air
temperature based on standard conditions at full rated flow.

7.3 MOISTURE REMOVAL SYSTEM

Liquid droplets are removed from the air stream in the separator. As the
air and liquid mixture passes through the separator it spins, slows down
and then changes direction. This causes the condensate to fall out of the
air stream and collect in the bottom of the separator. The collected liquid
is removed from the separator by a drain.

7.4  REFRIGERATION SYSTEM

The Refrigeration System consists of all the components which handle
R-404A. This is a hermetically sealed closed-loop system. Referring to
Figure 1 and following the phantom“

REFRIG

(

R

-

404

A

FLOW

,” refrigerant is

shown leaving the evaporator section where, in the process of removing
heat, it is changed from a low pressure liquid into a low pressure gas.
This gas enters the suction side of the compressor where it is
compressed into a high pressure gas. The high pressure gas is cooled
in the air cooled condenser section until it becomes a high pressure
liquid. It then goes through a permanent filter dryer that ensures the
refrigeration system is free of contaminants. A small diameter capillary
tube meters the refrigerant for introduction into the evaporator. The
refrigerant pressure is reduced upon entering the evaporator where as
it evaporates, removes heat from the thermal mass fluid.

7.5 THERMAL CIRCULATING SYSTEM

The thermal mass fluid in an Ingersoll Rand Nirvana Cycling dryer is
continuously circulated in a closed pump loop system. Referring to
Figure 1 and following the dashed “

THERMAL FLUID

” line, the heat is

removed from the fluid in the evaporator by the refrigeration system. The
thermal mass reservoir is sized to minimize refrigeration cycles during
reduced air load periods. The thermal mass fluid is pulled from the
bottom of the reservoir and pumped through the chiller, removing heat

from the air and then returned to the evaporator. The pump utilized on
the Ingersoll Rand Nirvana Cycling dryer is a maintenance-free, quiet
cartridge circulator pump similar to those used in residential water
systems. While the refrigeration system cycles on and off based on
loading conditions, the circulating pump runs continuously to maintain
flow through the chiller at all times. Note that when the power switch is
set to the off position, the circulating pump will not operate.

7.6 CONTROLS

The Ingersoll Rand Nirvana Cycling dryer incorporates automatic
controls for proper operation. The thermal mass fluid temperature is
maintained by a thermostat that monitors the temperature and cycles
the refrigeration system in response to varying air flow and temperature.
Upon an increase in the temperature of the thermal mass fluid, the
compressor is cycled on. When the fluid is cooled to its control set point,
the compressor is cycled off. The thermal mass fluid functions as a
thermal storage mass in the Nirvana Cycling dryer.

In addition to the factory set thermostat, a suction pressure gauge is
provided as standard equipment. This gauge monitors the pressure of
the refrigerant gas before it enters the compressor. When the
refrigeration system is running, the suction pressure will pull down to
between 55 to 65 psig, depending upon load and ambient conditions.
After the thermal mass fluid has been cooled and the refrigeration
system is shut off, the system pressure will equalize with a gauge
reading typically between 80 and 150 psig depending on ambient
temperature.

A “High Temp” alarm light is provided to indicate an elevated thermal
mass temperature. The light is controlled by a thermostat that monitors
the thermal mass and closes to energize the light at approximately 50°F.

FLOW DIAGRAM

FIGURE 1

Summary of Contents for D127NC

Page 1: ... 2007 REV B Ensure that the operator reads and understands the decals and consults the manuals before maintenance or operation Ensure that the Operation and Maintenance manual is not removed permanently from the machine Ensure that maintenance personnel are adequately trained competent and have read the Maintenance Manuals a ...

Page 2: ...7 3 MOISTURE REMOVAL SYSTEM 7 4 REFRIGERATION SYSTEM 7 5 THERMAL CIRCULATING SYSTEM 7 6 CONTROLS CONTENTS PAGE 8 0 INSTALLATION AND INITIAL START UP 6 8 1 LOCATION AND MOUNTING 8 2 PIPING AND VALVES 8 3 FILTRATION 8 4 ELECTRICAL CONNECTION 8 5 INITIAL START UP 9 0 SCHEDULED MAINTENANCE 7 9 1 INTRODUCTION 9 2 REFRIGERANT CONDENSER 9 3 CONDENSATE DISCHARGE SYSTEM 10 0 TROUBLESHOOTING 8 10 1 INTRODUC...

Page 3: ...placements or adjustments to the Equipment or any costs of labor performed by the Purchaser or others without Company s prior written approval The effects of corrosion erosion and normal wear and tear are specifically excluded Performance warranties are limited to those specifically stated within the Company s proposal Unless responsibility for meeting such performance warranties are limited to sp...

Page 4: ...ions completely before operating unit 3 Pull main electrical disconnect switch and disconnect any separate control lines if used before attempting to work or perform maintenance on the unit 4 Do not attempt to service any part while machine is in an operational mode 5 Do not attempt to remove any parts without first relieving the entire air system of pressure 6 Do not attempt to remove any part of...

Page 5: ...nsurance Rating Affected READ TECHNICAL MANUAL Removing fuses will not disconnect power from dryer Always disconnect power from ALL sources before performing service READ TECHNICAL MANUAL Air Under Pressure Will Cause Injury Death Or Property Damage Relieve Press Before Servicing Condensate Drain Discharges Under Pressure Drain Requires Periodic Cleaning Service READ TECHNICAL MANUAL HIGH VOLTAGE ...

Page 6: ...er section until it becomes a high pressure liquid It then goes through a permanent filter dryer that ensures the refrigeration system is free of contaminants A small diameter capillary tube meters the refrigerant for introduction into the evaporator The refrigerant pressure is reduced upon entering the evaporator where as it evaporates removes heat from the thermal mass fluid 7 5 THERMAL CIRCULAT...

Page 7: ...the filter that best suits your filtration requirements In addition to air filtration condensate discharge oil water separators are also available to address stringent EPA regulations 8 4 ELECTRICAL CONNECTION Equipment is available in various electrical configurations Providing power to these units is accomplished as follows 115V 1 60 These units are supplied with a three wire 115V cord assembly ...

Page 8: ...n and cleaning may be required An optional ambient air filter kit can be easily installed outside the condenser 9 3 CONDENSATE DISCHARGE SYSTEM On a minimum of a monthly basis the operation of the drain should be checked Periodically the drain should be removed and cleaned to ensure no debris from the system is trapped inside Ingersoll Rand Nirvana Cycling dryers are equipped with a drain isolatio...

Page 9: ...heck and clean condenser ambient air filter Check ambient temperature and reduce below 113 F Compressor relay may be bad replace relay Check for loose wire connections at contactor or loss of power at control board Inoperative pump or pump may have lost prime Check pump and contact Ingersoll Rand for priming instructions Contact your local distributor for further assistance Open valves Change filt...

Page 10: ... L1 N G FAN FOR ACTUAL COMPRESSOR TYPES REFER TO DRAWING 550059 COMPRESSOR CONNECTIONS A 2 MAIN INCOMING POWER DISCONNECT AND FUSING WILL BE PROVIDED BY CUSTOMER 3 POWER CONNECTION TO BE PROVIDED BY FACTORY SUPPLIED POWER CORD 6 CUSTOMER OPTIONAL CONNECTIONS SHOWN IN SMALL DASHED LINES 1 POWER REQUIREMENT PROVIDED BY CUSTOMER TO BE 120VAC 20A MAXIMUM FULL LOAD CURRENT AT 15A 7 RECEPTICAL FOR DRAIN...

Page 11: ...HT BLK GRN GRN GROUND LUG GRN BLK WHT WHT WHT WHT WHT BLK BLK GRN CONNECTIONS FAN BLK BLK TERMINAL STRIP CUSTOMER CONNECTION CONTACTOR COMPRESSOR BLK BLK WHT BLK BLK COMPRESSOR CONNECTIONS REFER TO DRAWING 550059 FOR ACTUAL COMPRESSOR TYPES L1 L2 2 MAIN INCOMING POWER DISCONNECT AND FUSING WILL BE PROVIDED BY CUSTOMER 1 POWER REQUIREMENT PROVIDED BY CUSTOMER TO BE 120VAC NOTES WHT HIGH TEMP ALARM ...

Page 12: ...ORD CONNECTOR OR OTHER CONNECTION TO BE PROVIDED BY USER 2 MAIN INCOMING POWER DISCONNECT AND FUSING WILL BE PROVIDED BY CUSTOMER 3 CUSTOMER POWER CONNECTION MADE WITH A 4 CORD 16 AWG 6 FT LONG POWER CORD PROVIDED WITH UNIT 6 CUSTOMER OPTIONAL CONNECTIONS SHOWN IN SMALL DASHED LINES 1 POWER REQUIREMENT PROVIDED BY CUSTOMER TO BE 200 240VAC 15A MAXIMUM FULL LOAD CURRENT AT 10A NOTES 5 OPTIONAL EQUI...

Page 13: ...IONS FAN BLK BLK CUSTOMER CONNECTION TERMINAL STRIP BLK BLK BLK BLK RED GRN L1 L2 COMPRESSOR CONNECTIONS REFER TO DRAWING 550059 FOR ACTUAL COMPRESSOR TYPES NOTES 1 MAIN INCOMING POWER DISCONNECT AND FUSING WILL BE PROVIDED BY CUSTOMER 2 FUSED OR CIRCUIT BREAKER DISCONNECT SWITCH TO BE PROVIDED BY OTHERS AND MUST MEET NEC CODE ALL WIRING TO BE IN ACCORDANCE WITH NEC AND ALL APPLICABLE CODES SEE EQ...

Page 14: ...SSOR ELECTRICAL CONNECTION TO COMPRESSOR G R O U N D CSIR TYPE CONNECTIONS COMPRESSOR 1 S R COMP C 1 3 BLK S START 2 R GRN BLK WHT D255NC A16 CSR TYPE G R O U N D COMPRESSOR CONNECTIONS 230V 1PH 60HZ COMP WHT BLK OL 3 S R C RED 1 BLK GRN RED BLK RED GND BLK RUN ENCLOSURE CAPACITOR RELAY AND COMPRESSOR START 4 4 5 1 2 220V 1PH 50HZ 115V 1PH 60HZ 110V 1PH 50HZ D127NC A16 CSIR TYPE D212NC A16 CSIR TY...

Page 15: ...12NC D255NC AIR INLET CONNECTION 1 MPT D127NC D170NC 1 1 2 MPT D212NC D255NC SUCTION PRESSURE GAGE HIGH TEMPERATURE LIGHT ON OFF SWITCH WITH POWER ON LIGHT 29 38 27 38 31 44 1 75 16 00 14 25 19 35 12 550060 GENERAL ARRANGEMENT D127NC A16 THRU D255NC A16 NEMA 1 FRONT VIEW RIGHT SIDE VIEW LEFT SIDE VIEW TOP VIEW GENERAL ARRANGEMENT D127NC THRU D255NC NEMA 1 ...

Page 16: ...PT D127NC D170NC 1 1 2 MPT D212NC D255NC SUCTION PRESSURE GAGE ON OFF SWITCH WITH POWER ON LIGHT HIGH TEMPERATURE ALARM LIGHT 29 38 27 38 1 75 TYP 16 00 14 25 19 31 44 23 56 550061 GENERAL ARRANGEMENT D127NC A16 THRU D255NC A16 NEMA 4 FRONT VIEW RIGHT SIDE VIEW LEFT SIDE VIEW TOP VIEW A DETAIL A 12 0 GENERAL ARRANGEMENT GENERAL ARRANGEMENT D127NC THRU D255NC NEMA 4 ...

Page 17: ...141575 23141575 15 Light Hi Temp 23141377 23141385 23141385 23141377 23141385 23141385 23141377 23141385 23141385 23141377 23141385 23141385 16 Tstat High Temp 21341369 21341369 21341369 21341369 21341369 21341369 21341369 21341369 21341369 21341369 21341369 21341369 17 Tstat Operational 21341369 21341369 21341369 21341369 21341369 21341369 21341369 21341369 21341369 21341369 21341369 21341369 18 ...

Page 18: ...70NC A16 1 115 1 60 1 2 9 2 36 0 1 1 18 1 80 2 3 R404 1 14 0 852 20 14 2 300 136 0 D170NC A16 2 230 1 60 1 2 4 9 25 9 1 1 18 0 90 1 2 R404 2 3 0 994 10 7 5 300 136 0 D212NC A16 1 115 1 60 3 4 15 0 57 0 1 1 18 1 80 2 3 R404 2 0 0 909 20 13 2 300 136 0 D212NC A16 2 230 1 60 3 4 6 5 30 0 1 1 18 0 90 1 2 R404 2 0 0 909 15 9 5 300 136 0 D255NC A16 1 115 1 60 1 15 0 71 0 1 1 18 1 80 2 3 R404 2 3 0 994 2...

Reviews: