3.6.1 Auto Restart- This setpoint is used to enable or
disable the auto restart option.
3.6.2 Auto Restart Time- This setpoint is the minimum
time period the compressor must run unloaded before
it can stop in the auto restart mode.
3.6.3 Auto Restart Delay Time- If the compressor is
stopped in auto restart, this setpoint is the number of
seconds the package discharge pressure must remain
below the online pressure setpoint before the
compressor will restart.
3.6.4 Sequencer- This setpoint is used to enable or
disable sequencer operation.
3.6.5 Remote Start/Stpop- This setpoint is used to
enable or disable the remote start/stop option.
3.6.6 Power Out Restart- This setpoint is used to
enable or disable the power out restart option, if it is
installed.
3.7.7 Power Out Restart Time- If the power out
restart option is installed and enabled, this setpoint is
time period between power returning to the
compressor and the compressor starting.
3.6.8 Low Ambient- This setpoint enables or disables
the low ambient option. If the low ambient option is
enabled, sensor 3CTT must be installed in the
compressor.
3.6.9 Minimum Cooler Out Temperature- When the
low ambient option is installed, this setpoint is the
minimum temperature to which the coolant must rise
before the compressor will load.
3.6.10 Separator Delta-P Solenoid- This setpoint
enables or disables the separator delta-p solenoid
option. Enabling this option will automatically disable
the Separator Delta-P Sensor option.
3.6.11 Separator Delta-P Sensor- This setpoint
enables or disables the separator delta-p sensor
option. Enabling this option will automatically disable
the Separator Delta-P Solenoid option.
3.6.12 Lead/Lag Cycle Length- This setpoint enables
the automatic cycling between lead and lag operation.
If it is set to a value greater than 0, the controller will
cycle between lead and lag operation. The value of this
set point is the cycle length in real time hours. A value
of 0 will disable the automatic cycling between lead
and lag.
3.6.13 Scheduled Start- If the scheduled start/stop
option is installed, this set point is the time of the day
(hour and minute) that the compressor will
automatically start. To disable this option, set it to the
same value as the scheduled stop (section 3.6.14).
3.6.14 Scheduled Stop- If the scheduled start/stop
option is installed, this setpoint is the time of the day
(hour and minute) that the compressor will
automatically stop. To disable this option, set it to the
same value as the scheduled start (section 3.6.13).
3.6.15 High Dust Filter- This option enables or
disables the high dust filter operation.
3.6.16 Modbus Protocol- This option is for Ingersoll-
Rand service use only.
3.6.17 Modbus Address- This feature is used with the
Modbus Protocol and is for Ingersoll-Rand service use
only.
3.6 OPTIONS (CONTINUED)
Summary of Contents for 100-200
Page 17: ...FIGURE 2 5 1 TYPICAL OUTDOOR SHELTERED INSTALLATION 15...
Page 18: ...16 3 0 INTELLISYS INTELLISYS CONTROLLER INGERSOLLrAND INTELLISYS...
Page 52: ...50 54418074 REV B 8 0 REFERENCE DRAWINGS 8 1 ELECTRICAL SCHEMATIC STAR DELTA...
Page 53: ...51...
Page 54: ...52 54622865 REV B 8 2 FOUNDATION PLAN 125 150 HP 90 110KW AIRCOOLED SINGLE STAGE CONTINUED...
Page 55: ...53 54622865 REV B 8 2 FOUNDATION PLAN 125 150 HP 90 110 KW AIRCOOLED SINGLE STAGE...
Page 56: ...8 3 FOUNDATION PLAN 200 HP 132 160 KW AIRCOOLED SINGLE STAGE CONTINUED 54622931 REV B 54...
Page 57: ...8 3 FOUNDATION PLAN 200 HP 132 160 KW AIRCOOLED SINGLE STAGE 54622931 REV B 55...
Page 58: ...56 8 4 FOUNDATION PLAN 125 150 HP 90 110 KW WATERCOOLED SINGLE STAGE CONTINUED 39925300 REV C...
Page 59: ...57 8 4 FOUNDATION PLAN 125 150 HP 90 110 KW WATERCOOLED SINGLE STAGE 39925300 REV C...
Page 60: ...58 8 5 FOUNDATION PLAN 200 HP 132 160 KW WATERCOOLED SINGLE STAGE CONTINUED 39926191 REV C...
Page 61: ...59 8 5 FOUNDATION PLAN 200 HP 132 160 KW WATERCOOLED SINGLE STAGE 39926191 REV C...
Page 62: ...60 8 6 FOUNDATION PLAN AIRCOOLED CONTINUED 100 150 HP 75 110 KW TWO STAGE 54622980 REV B...
Page 63: ...61 54622980 REV B 8 6 FOUNDATION PLAN AIRCOOLED 100 150 HP 75 110 KW TWO STAGE...
Page 64: ...62 8 7 FOUNDATION PLAN AIRCOOLED CONTINUED 200 HP 132 160 KW TWO STAGE 54623053 REV B...
Page 65: ...63 54623053 REV B 8 7 FOUNDATION PLAN AIRCOOLED 200 HP 132 160 KW TWO STAGE...
Page 66: ...64 8 8 FOUNDATION PLAN WATERCOOLED CONTINUED 100 150 HP 75 110 KW TWO STAGE 39925326 REV C...
Page 67: ...65 8 8 FOUNDATION PLAN WATERCOOLED 100 150 HP 75 110 KW TWO STAGE 39925326 REV C...
Page 68: ...66 8 9 FOUNDATION PLAN WATERCOOLED CONTINUED 200 HP 132 160 KW TWO STAGE 39926340 REV C...
Page 69: ...67 8 9 FOUNDATION PLAN WATERCOOLED 200 HP 132 160 KW TWO STAGE 39926340 REV C...
Page 70: ...68 8 10 FLOW SCHEMATIC AIRCOOLED SINGLE STAGE 54579081 REV A...
Page 71: ...69...
Page 72: ...70 8 11 FLOW SCHEMATIC WATERCOOLED 90 F 32 C SINGLE STAGE 54579503 REV A...
Page 73: ...71...
Page 74: ...72 8 12 FLOW SCHEMATIC WATERCOOLED 115 F 46 SINGLE STAGE 54579511 REV A...
Page 75: ...73...
Page 76: ...74 8 13 FLOW SCHEMATIC AIR COOLED TWO STAGE 54579644 REV A...
Page 77: ...75...
Page 78: ...76 8 14 FLOW SCHEMATIC WATERCOOLED 90 F 32 C TWO STAGE 54579693 REV A...
Page 79: ...77...
Page 80: ...78 8 15 FLOW SCHEMATIC WATERCOOLED 115 F 46 C TWO STAGE 54579727 REV A...
Page 81: ...79...
Page 82: ...80 8 16 TYPICAL SYSTEM FLOW DIAGRAMS TYPICAL SYSTEM FLOW DIAGRAM...
Page 83: ...81 8 16 TYPICAL SYSTEM FLOW DIAGRAMS...
Page 84: ...82 8 16 TYPICAL SYSTEM FLOW DIAGRAMS...
Page 85: ...83 8 16 TYPICAL SYSTEM FLOW DIAGRAMS...
Page 86: ...84 8 16 TYPICAL SYSTEM FLOW DIAGRAMS...
Page 90: ...88 DATE RUN TIME WORK DONE QTY UNIT WORK HOURS MEASURE BY 10 0 MAINTENANCE RECORD...
Page 91: ...89 DATE RUN TIME WORK DONE QTY UNIT WORK HOURS MEASURE BY MAINTENANCE RECORD...
Page 92: ...90 DATE RUN TIME WORK DONE QTY UNIT WORK HOURS MEASURE BY MAINTENANCE RECORD...
Page 93: ...91 DATE RUN TIME WORK DONE QTY UNIT WORK HOURS MEASURE BY MAINTENANCE RECORD...