9.2. List of alarms and reasons for shutdown
The following table details the possible reasons for each alarm.
Code
Alarm
Reason for shutdown
Description
0000H
None
No alarm, the unit must be connected whenever it
has enough power.
0001H
Frequency
Grid frequency out of range.
Grid frequency out of range.
0002H
Voltage
Grid voltage out of range
Grid voltage out of range
0004H
Current loop
Internal current loop fault.
Internal current loop fault.
0008H
Reset
Reset
Indicates that the inverter has reset, inverter
firmware fault
0010H
Effective grid current
Effective grid current
RMS current exceeds maximum allowed
0020H
Temperature
Power electronics temperature.
The temperature of power electronics exceeds
176 °F (80 °C).
Auxiliary temperature sensor
The auxiliary temperature sensor has triggered an
alarm
0080H
Instantaneous grid
current
Instantaneous grid current
Instantaneous current value out of range
0100H
AC protections
Varistors
Error in AC varistors
Contactor
The state of the contactor is not correct for the
current inverter status.
AC protections
Error in some of the AC protectors, arresters, fuses,
etc.
Thermomagnetic circuit breaker Error in the three-phase input thermomagnetic
circuit breaker.
0200H
DC protections
DC protections
Blown DC input fuse or DC arresters
0400H
AC insulation
AC insulation
Insulation fault in the PV array on inside the inverter
Varistors
Error in DC varistors
0800H
Branch fault alarm
Fault in branch #1
Fault in branch #1 of the power electronics
Fault in branch #2
Fault in branch #2 of the power electronics
Fault in branch #3
Fault in branch 3 of the power electronics
1000H
Manual shutdown
Manual shutdown
Manual shutdown due to the limit switch, via the
display or communications
2000H
Configuration
Configuration
Shutdown due to a change in firmware
Firmware
Shutdown due to firmware load
4000H
High input voltage
High input voltage
High DC input voltage
8000H
Panel voltage
Low input voltage
Shutdown due to low input voltage.
Hardware fault
Reason for internal shutdown, hardware failure
Low power
Shutdown due to low power, (typical at nightfall)
Fatal error
Due to five consecutive errors in the branches, or
consecutive contactor shutdowns.