EonStor DS B12/B24 Series
136
Replacing the FBM (2U systems)
NOTE
The FBM on 2U systems type II controllers are not user maintainable. Please
contact your vendor for upgrades or technical support, if suspect a fault.
To replace the FBM, follow these steps:
1
1
2
3
4
5
1. Remove the controller module from the chassis (refer to
2. Remove the BBU module (see the previous section).
3. Remove the top screw
(1)
and side screw
(2)
of the top cover
(3)
from the
controller chassis.
4. Pull the retention latches
(4)
away from the FBM
(5)
. Use your finger nails if the
FBM does not easily disengage. Once disengaged, the flash module will pop up.
You can then remove it from the socket.
5. Insert the replacement FBM into the socket at a 15 degree angle. When fully
inserted, press the flash module down until it is snapped by the retention latches.
6. Reinstall the BBU (refer to
) and the controller (refer to
Installing the RAID Controller
128