9.15. Input voltage high/Input voltage low Alarms
If the input voltage is not within the specified limits, these alarms appear. In this case, UPS operates
in Battery Operation mode, as soon as the mains returns to specified limits, then the alarm shall
dissappear.
If the mains does not return to normal conditions during Battery Operation, UPS will
be
turned off and all loads at the output would be deenergized at the end of battery
autonomy.
9.16. Bypass voltage high/ Bypass voltage low Alarms
If the bypass voltage is not within the specified limits, these alarms appear. In this case, UPS operates
in Online Operation mode, as soon as the mains returns to specified limits, the alarm shall dissappear,
but never switches to Bypass Operation. If UPS needs to be switched to bypass at this moment, UPS
will cut the output and load would be deenergized.
9.17. Inverter temperature high/ Rectifier temperature high Alarms
If temperature of the inverter or rectifier block rises, these alarms appear. The reasons can be;
overload (see
), broken fans and high ambient temperature (see
). If the fans
are broken or any other problem is defined, contact to an authorized Technical Service.
9.18. Junction/Heatsink temperature high Alarms
If temperature of the heatsink or junction rises up, these alarms appear. The reasons can be; overload
(see
), broken fans and high ambient temperature (see
). If the fans are
broken or any other problem is defined, contact to an authorized Technical Service.
Any other alarm occurs except the alarms explained above, contact to an authorized Technical
Service instantly.
Please have the following information ready before you contact to service:
Ensure you read the troubleshooting section carefully and apply the procedure.
Model Number
Serial Number
Firmware version
Date of failure or problem
Symptoms of failure or problem
Customer return address and contact information
Summary of Contents for ETR EVO Series
Page 16: ...ETR EVO UPS User Manual Ver 1 0 Page 11 10 15kVA 3Ph Input 3Ph Output Terminal Connections...
Page 17: ...ETR EVO UPS User Manual Ver 1 0 Page 12 20 30kVA 3Ph Input 3Ph Output Terminal Connections...
Page 18: ...ETR EVO UPS User Manual Ver 1 0 Page 13 40 60kVA 3Ph Input 3Ph Output Terminal Connections...
Page 19: ...ETR EVO UPS User Manual Ver 1 0 Page 14 80kVA 3Ph Input 3Ph Output Terminal Connections...
Page 20: ...ETR EVO UPS User Manual Ver 1 0 Page 15 100kVA 3Ph Input 3Ph Output Terminal Connections...
Page 21: ...ETR EVO UPS User Manual Ver 1 0 Page 16 120kVA 3Ph Input 3Ph Output Terminal Connections...
Page 22: ...ETR EVO UPS User Manual Ver 1 0 Page 17 160kVA 3Ph Input 3Ph Output Terminal Connections...
Page 23: ...ETR EVO UPS User Manual Ver 1 0 Page 18 200kVA 3Ph Input 3Ph Output Terminal Connections...
Page 36: ...ETR EVO UPS User Manual Ver 1 0 Page 31...
Page 71: ...ETR EVO UPS User Manual Ver 1 0 Page 66 40 200kVA Standard UPS 40 200kVA UPS with Split Bypass...