background image

5

sensor

2.  Installation

Remove the Thermostat Face

1.

 Remove the thermostat Front Module 

from the Power Module by opening the door 

and loosening the screw.

2.

  Pull outward near the bottom on the 

Front Module and lift off.

Prepare the Wiring

1.

 Find a location for your thermostat.  It 

is suitable for indoor use only, on insulated 

or uninsulated walls.  Locate it about 4

1

2

 feet to 5 feet above the 

oor on an 

inside wall.  Make sure it is well ventilated and not located in a con

ned space 

such as a small closet or cabinet. Avoid placing it near other heat sources such 

as hot-water piping, heat duct, wall-mount lighting, and direct sunlight to help 

prevent adversely affecting the thermostat.

2.

  Turn off the power to the 

oor warming system at the main circuit panel 

before doing any electrical work.

3.

  A quali

ed electrician should run a dedicated circuit from the main circuit 

panel to the thermostat location.

4.

  If a dedicated circuit is not possible, you may tap from another circuit in the 

room.  Make sure there is enough load capacity (amps) to handle the addition 

of your 

oor warming system, and that it is NOT wired in series with any other 

device, including other GFCIs.

5.

  The circuit breaker in the main circuit panel should be 15 amps maximum 

29050V1 Programmable Thermostat

Owner’s Manual

Your new Infloor Pro thermostat

 is designed to control the voltage to 

either a 120VAC or 240VAC resistive 

oor warming system.

Please follow this manual for complete installation and operation instructions.  

If you have any questions or comments, try calling Technical Support at  

800 608-0562.

  CAUTION

:  Make sure you are quali

ed and are familiar with house wiring.  

This is a line voltage device that could cause serious injury or damage if 

improperly installed.

Connect Wires

1.

 Match and connect the two 

wires marked “LINE1” and 

“LINE2” to the power supply wires 

using the wire nuts provided.

2.

  Gently tug on the wires to make 

sure they are secure, otherwise 

wire could loosen and cause 

failure.

3.

  Overwrap the wire nuts with 

electrical tape to better secure 

them to the wires.

4.

  Match and connect the two 

wires marked “LOAD1” and 

“LOAD2” to the 

oor warming 

system lead wires and secure 

these wires the same way.

5.

  Connect the house ground wire 

to the green or bare lead wire(s) of 

your 

oor warming system.

6.

  Insert the ends of the 

oor 

sensor wire into the “SENSOR” 

terminals (1 and 2) and tighten 

the screws.  There is no polarity, 

so it does not matter which wire 

end goes into which terminal.

  CAUTION: 

 Before continuing, 

make sure your power supply 

voltage matches the voltage rating 

of your 

oor warming system.  

Connecting 240V to a 120V 

oor 

warming system will cause overheating and damage to the system and may 

damage the control, other wiring, 

oor coverings, etc.

Remote Control

1.

 If you want to connect your thermostat to a remote control device, such as 

a home automation system, 

rst make sure that the remote device has a “dry 

contact” output (an un-energized switch, such as the contacts on a relay).  Many 

home automation systems come with such an output that opens or closes at 

speci

ed times.

2.

  Pull 2-conductor wire, size 18- to 24-gage, through the wall from the remote 

device, into this electrical box.

3.

  Connect the wire ends into the “SETBACK” terminals (5 and 6) and tighten 

the screws (no polarity).

 

Infloor 29053V1 Relays

1.

 If you want to use your thermostat to drive a 29053V1 Relay(s) (ask your dealer 

about this convenient way to control larger systems with one thermostat), 

rst 

read and follow the instructions for the Infloor Relay thoroughly.

2.

  Pull 2-conductor wire, size 18- to 24-gage, through the wall from the Infloor 

Relay, into this electrical box.  This wire may be up to 100 feet (30 m) in length 

from the thermostat to the last Infloor Relay installed.

3.

  Connect the wire ends into the “RELOUT” terminals (3 and 4) and tighten the 

screws(Observe polarity of the wires when connecting to the Infloor 29053V1 Relay).

 

Mount the Thermostat

1.

 Carefully fold and press the wires 

back into the electrical box.  Do not use 

the thermostat to push them in, as this 

may cause connections to loosen and 

possible failure.

2.

  Secure the thermostat Power Module 

into the box with the mounting screws 

provided.

3.

  Carefully snap the Front Module onto 

the Power Module.

4.

  Tighten the screw.

5.

  Switch on the power at the main circuit 

panel.

3.

  Press the HOLD/RETURN button or wait 15 seconds and the thermostat will 

return to the normal operating mode, saving your selection.  The thermostat 

will now display a 

P1

P2

P3

, or 

P4

 at the bottom right.

3.  Quick Setup

On/Off Switch

Your thermostat should be turned off when it 

is 

rst installed.  The display will show 

OFF

 and 

the time and day.

1.

 Slide the on/off switch to the upper position, 

turning the thermostat on.  The display will 

show the time and day, temperatures, and other 

information.

2.

  To turn the thermostat off anytime, slide the 

on/off switch to the lower position.  No heating 

will occur and all programming is retained.

Change Format Between °F / 12-hour and °C / 24-hour

Your thermostat is factory set to operate in either °F / 12 hour format or °C / 

24 hour (military time) format.  If needed, you may change this at any time as 

follows:

1.

 Press the OPTIONS button and hold for 1 second.  An °

F

 and 

12h

 will show on the display.

2.

  Press the down or up button to toggle to °

C

 and 

24h

.

3.

  Press the HOLD/RETURN button to return to the normal 

operating mode.

Set the Current Time and Day

1.

 Press the DAY/TIME button and hold for 1 second.  The hour should be 

blinking.

2.

  Press the down or up button to adjust the hour.

3.

  Press the DAY/TIME button brie

y.  The minutes should be 

blinking.

4.

  Press the down or up button to adjust the minutes.

5.

  Press the DAY/TIME button brie

y.  The day should be blinking.

6.

  Press the down or up button to adjust the day.

7.

  Press the HOLD/RETURN button or wait 15 seconds and the 

thermostat will return to the normal operating mode, saving your settings.

MO

SET TEMP

FLOOR

CYCLE

M

A

°F

1-4

Customized Program Schedule (User)

To customize the program shedule to meet your needs, follow 

these steps:

1.

 Press the PROGRAM button and hold for 1 second.  

Pro

 and 

U1, P1, P2, P3, 

or

 P4

 will show on the display.

2.

 Press the down or up button to select 

U1

.

3.

 Press the PROGRAM button brie

y.  

CYCLE 1

 and 

MO

 through 

FR

 will show on the display.  The hour should be blinking. 

4.

 Press the down or up button to adjust the hour.

5.

 Press the PROGRAM button brie

y.  The minutes should be 

blinking.

6.

 Press the down or up button to adjust the minutes.

7.

 Press the PROGRAM button brie

y.  The setpoint temperature 

should be blinking.

8.

 Press the down or up button to adjust the setpoint temperature.

  Note:

  A good rule of thumb is to adjust this about 5 to 8°F (3 to 5 °C) 

  lower during cycles when you are away to help reduce energy use.  If you 

  set the “away” cycles too low, it will take much longer to raise the 

  temperature again and may result in unsatisfying performance.

  Note:

  Some wood and laminate 

oor manufacturers recommend a 

  maximum of 82 to 84°F (27° to 28°C). Check with manufacturer.

9.

 Press the PROGRAM button brie

y to move to the next cycle number.

10.

  Repeat Steps 3 through 7 to adjust the remaining cycle times and setpoint 

temperatures 

MO

 through 

FR

, and for the other days of the week.

11.

  When you 

nish, or at any time during these adjustments, press the 

HOLD/RETURN button or wait 30 seconds and the thermostat will return to the 

normal operating mode.  Your adjustments will be saved.

Note:

  The display in normal operating mode will not show a “U1” indicating 

“User” schedule.  Also, all schedule adjustments are saved in memory and 

will not be lost during power failure.

Note:

  If you only want to use two cycles during a day, clear the other cycles by 

reducing their temperature below 40°F (4.5°C) to show (---).  

To use these cycles again, adjust their time and temperature.

from 

power 

supply

on/off

MO

M

A

SET TEMP

LIMIT

FLOOR

°F

MO

°C

AIR

SET TEMP

SET BACK

LIMIT

FLOOR

USAGE

CYCLE

M

A

M

P

M

A

M

P

°C

°F

°C

°F

TUWE THFR SASU

HOLD

GFCI

TRIP

HEATING

°F

P1

P2

P3

P4

LOCK

MO

M

A

HEATING

MO

SET TEMP

CYCLE

M

A

°F

HOLD

USAGE

MO

CYCLE

M

A

°F

TUWE THFR

MO

CYCLE

M

A

°F

SET BACK

FLOOR

FLOOR

MO

CYCLE

M

A

°F

FLOOR

Use the Factory Programmed “User” Schedule

If you want to begin using your thermostat now without making any changes to 

the factory set programming schedule, you may skip to section “

5  Operation

”.  

It will operate in the “User” Schedule (U1), pre-programmed as follows, and 

can be customized later to your needs (see section “

4  Additional Setups

”):

4.  Additional Setups

Lifestyle Program Schedules (Presets)

There are convenient schedules already set up to meet typical lifestyles.  If you 

see a schedule P1 through P4 you like, select one as follows:

1.

 Press the PROGRAM button and hold for 1 second.  

Pro

 and 

U1, P1, P2, P3, 

or

 P4

 will show on the display. 

2.

  Press the down or up button brie

y to select 

P1

P2

P3

, or 

P4

.  

These schedules are not able to be modi

ed, and are as follows:

MO

M

A

SET TEMP

LIMIT

FLOOR

°F

MO

°C

AIR

SET TEMP

SET BACK

LIMIT

FLOOR

USAGE

CYCLE

M

A

M

P

M

A

M

P

°C

°F

°C

°F

TUWE THFR SASU

HOLD

GFCI

TRIP

HEATING

°F

P1

P2

P3

P4

LOCK

MO

M

A

HEATING

MO

SET TEMP

CYCLE

M

A

°F

HOLD

USAGE

MO

CYCLE

M

A

°F

TUWE THFR

MO

CYCLE

M

A

°F

SET BACK

FLOOR

FLOOR

MO

CYCLE

M

A

°F

FLOOR

MO

M

A

MO

°C

AIR

SET TEMP

SET BACK

LIMIT

FLOOR

USAGE

CYCLE

M

A

M

P

M

A

M

P

°C

°F

°C

°F

TUWE THFR SASU

HOLD

GFCI

TRIP

HEATING

°F

P1

P2

P3

P4

LOCK

MO

CYCLE

M

A

°F

TUWE THFR

MO

M

A

SET TEMP

LIMIT

FLOOR

°F

MO

°C

AIR

SET TEMP

SET BACK

LIMIT

FLOOR

USAGE

CYCLE

M

A

M

P

M

A

M

P

°C

°F

°C

°F

TUWE THFR SASU

HOLD

GFCI

TRIP

HEATING

°F

P1

P2

P3

P4

LOCK

MO

M

A

HEATING

MO

SET TEMP

CYCLE

M

A

°F

HOLD

USAGE

MO

CYCLE

M

A

°F

TUWE THFR

MO

CYCLE

M

A

°F

SET BACK

FLOOR

FLOOR

MO

CYCLE

M

A

°F

FLOOR

to

floor 

warming 

system

1.  Preparation

1.

 Unpack your thermostat and make sure everything is in good condition:

Thermostat

• 

Floor sensor

• 

Small screwdriver

• 

Mounting screws

• 

Wire nuts for wiring connections

• 

If any parts are missing or damaged, contact the store where you purchased 

this thermostat.  Do not install a damaged part.

2.

  Gather the following tools and supplies:

 

Phillips screwdriver, hole saw

 

Wire strippers, “

sh tape”, other electrical tools

 

Electrical box for thermostat:

 

a.

 If you are connecting to power leads from only 1 or 2 

oor warming 

 

systems, you may use a single-gang, 3

1

2

 inch deep box.

 

b.

 If you are connecting to power leads from 3 

oor warming systems, 

 

use a 4x4x2

1

inch or deeper box (not a 2-gang box) when your wall studs 

 

are still exposed. Install a single-gang “mud-ring” cover on the box before 

 

installing drywall materials.

 

c.

 For more than 3 

oor warming systems or other layouts, you may need 

 

to install a junction box to connect the power leads together. Then use 

 

house wire to connect between the junction box and the thermostat 

 

electrical box. See the installation instructions for your 

oor warming 

 

system for more information.

 

ALWAYS

:  Wire all circuits as Class 1, Electric Light and Power Circuits.

 

ALWAYS

:  Wire all circuits with insulation rated 600V minimum.

 

ALWAYS

:  Mount this control only to a grounded metallic box or a 

  nonmetallic box.

 

ALWAYS

:  Use power supply wires suitable for at least 90°C.

 

 

CAUTION

:  High voltage – disconnect power supply before servicing.

for a 

oor warming system totaling 12 amps or less.  For larger systems up 

to 15 amps, use a 20 amp maximum circuit breaker. Never exceed 15 amps 

on this thermostat.  You may consider using an arc-fault (AFCI) type circuit 

breaker for additional protection.

6.

  Pull the power supply wiring into this box, leaving about 6 inches of wire.

7.

  Pull the 

oor sensor wire and the power lead wires from your 

oor warming 

system up the wall, into this box.  Refer to your 

oor warming system 

installation instructions for placement of the 

oor sensor tip into the 

oor area.

Note:

  The sensor wires should not be run in the same conduit as line voltage 

wires to avoid possible interference.  If the sensor lead wires are not long 

enough, they may be extended an additional 15 feet (4.5 m) using minimum 

20-gage 2-conductor wire or up to 50 feet (15 m) using shielded wire.

 

8.

  Mount the electrical box. 

power 

module

front 

module

MO

M

A

SET TEMP

LIMIT

FLOOR

°F

MO

°C

AIR

SET TEMP

SET BACK

LIMIT

FLOOR

USAGE

CYCLE

M

A

M

P

M

A

M

P

°C

°F

°C

°F

TUWE THFR SASU

HOLD

GFCI

TRIP

HEATING

°F

P1

P2

P3

P4

LOCK

MO

M

A

HEATING

MO

SET TEMP

CYCLE

M

A

°F

HOLD

USAGE

MO

CYCLE

M

A

°F

TUWE THFR

MO

CYCLE

M

A

°F

SET BACK

FLOOR

FLOOR

MO

CYCLE

M

A

°F

FLOOR

Cycle

1

2

3

4

Mon-Fri

6:00 am

8:00 am

5:00 pm

10:00 pm

82 F

74 F

82 F 

74 F 

Saturday

7:00 am

9:00 am

5:00 pm

11:00 pm

82 F

74 F

82 F

74 F

Sunday

7:00 am

9:00 am

5:00 pm

11:00 pm

82 F

74 F

82 F

74 F

U1 (User changeable)

82 F

82 F

74 F

74 F

Note:

  Air Sensing mode default temperatures are 70F and 62F.

Cycle

1

2

3

4

Mon-Fri

5:00 am

7:00 am

5:00 pm

10:00 pm

82 F

74 F

82 F 

74 F 

Saturday

5:00 am

9:00 am

5:00 pm

10:00 pm

82 F

74 F

82 F

74 F

Sunday

5:00 am

9:00 am

5:00 pm

10:00 pm

82 F

74 F

82 F

74 F

P1 (Early Riser)

Note:

  Air Sensing mode default temperatures are 70F and 62F.

Cycle

1

2

3

4

Mon-Fri

5:00 am

8:00 am

6:00 pm

11:00 pm

82 F

74 F

82 F 

74 F 

Saturday

6:00 am

9:00 am

5:00 pm

11:00 pm

82 F

74 F

82 F

74 F

Sunday

6:00 am

9:00 am

5:00 pm

11:00 pm

82 F

74 F

82 F

74 F

P2 (Longer Day)

Note:

  Air Sensing mode default temperatures are 70F and 62F.

Cycle

1

2

3

4

Mon-Fri

6:00 am

9:00 am

6:00 pm

10:00 pm

75 F

70 F

75 F 

70 F 

Saturday

7:00 am

10:00 am

6:00 pm

10:00 pm

75 F

70 F

75 F

70 F

Sunday

7:00 am

10:00 am

6:00 pm

10:00 pm

75 F

70 F

75 F

70 F

P4 (Take the chill off)

Note:

  Air Sensing mode default temperatures are 65F and 60F.

Cycle

1

2

3

4

Mon-Fri

6:00 am

8:00 am

6:00 pm

10:00 pm

82 F

79 F

82 F 

75 F 

Saturday

6:00 am

9:00 am

6:00 pm

10:00 pm

82 F

79 F

82 F

75 F

Sunday

6:00 am

9:00 am

6:00 pm

10:00 pm

82 F

79 F

82 F

75 F

P3 (At home during the day)

Note:

  Air Sensing mode default temperatures are 70F, 67F, and 62F.

Example

Cycle

1

2

3

4

Mon-Fri

--:--

7:30 am

6:00 pm

--:-- 

--

 F

72 F

80 F 

--

 F 

80 F

80 F

72 F

NOTE to contractors:

 

After installing the thermostat, be sure to:

 

a.

 

Do a Quick Setup (section 3),

 

b.

 

Temporarily override the setpoint temperature to make sure it is 

   

heating for a few minutes (section 5),

 

c.

  Test the GFCI (section 5).

P

Reviews: