background image

Before you Begin

This document presents a method for assessing buoyancy control 

needs for Infiltrator Water Technologies (Infiltrator) IM-Series tanks. 

Tank buoyancy control measures must be implemented according to 

state and/or local regulations, which may supersede these guidelines. 

If unsure of the requirements for a particular site, contact the local 

health department or permitting authority.

If tank buoyancy control measures are implemented, refer to Infiltrator 

IM-Series Tank Installation Instructions and Riser Connection 

Guidance documents, as applicable, for completing the installation.

How to Use this Document

1. Using Step 1, Table 1 and Figures 1 and 2, verify that the water level 

outside the tank is below the outlet pipe saddle height and determine if 

buoyancy control is required.

2. Use the appropriate row in Step 2, Table 2 to determine the minimum 

buoyancy control methods for the site conditions.

3. Once the preferred buoyancy control method is selected, follow the  

implementation procedures provided in Step 3.  

Step 1 – Determine Need for Buoyancy Control

Required information: (1) maximum height of water outside the tank and 

above the tank bottom; and (2) the depth of soil cover above the tank top. 

Tank buoyancy control may be required if:

• the water level outside the tank has the potential to rise 30 inches (750 

mm) or more above the bottom of the tank; and

• less than 12 inches (300 mm) of soil cover is to be placed as backfill over 

the tank top. 

Allowable Subsurface Water Elevation

Groundwater elevation, groundwater table, and water table are terms for 

the subsurface condition where water is held in the subsurface soil pores 

or rock. The seasonal high groundwater elevation represents the sustained 

highest point the water table has the potential to reach at any time of the 

year. That point is not necessarily the level at which groundwater may be 

observed seeping from the soil at the time of tank installation. In general, 

a qualified soil evaluator or engineer can estimate the seasonal high 

groundwater elevation from careful examination of the soil profile. 

Under certain conditions, a perched water table may be present in the 

subsurface. A perched water table occurs where there is an impermeable 

or low-permeability soil that causes water to be present in the soil pores 

above the main water table. A perched water table elevation may exceed the 

seasonal high elevation of the main water table. The vertical position of the 

tank must account for both the seasonal high groundwater table and any 

existing or future perched water table condition. Verify that the subsurface 

water elevation will not exceed the height of the outlet pipe saddle of 

the tank, as shown in Figure 1 and described in Table 1.

Table 1 Instructions

 1.    In the left-hand column of Table 1, locate the row corresponding to the 

height of the water elevation outside the tank and above the tank bottom 

(Parameter I) for the site conditions. See Figure 2.

  2.   Follow that row to the right until reaching the column corresponding to 

the depth of soil cover proposed above the tank top (Parameter II). See 

Figure 2.

 3.  If the tank model is listed in that cell, then buoyancy control is required 

(proceed to Step 2). If the tank model is not listed in that cell, then no 

buoyancy control is required.

 4.  IM-Series tanks shall not be installed where the water level outside the 

tank exceeds the height of the outlet pipe saddle.

Infiltrator IM-Series Tank 

Buoyancy Control Guidance

OCTOBER 2016

Table 1:  

Infiltrator Tank Models

1

 and Conditions Requiring Buoyancy Control

Parameter I: 

Water height

2

 above tank bottom

Parameter II:  

Soil cover depth above tank top

3

A

B

6 in (150 mm) to  

12 in (300 mm)

Above 12 in

(300 mm)

1

Above outlet pipe saddle

 

(greater than 43” [1,075 mm])

Do not install

Do not install

2

36” (900 mm) to 43” (1,075 mm)  

(to outlet pipe saddle)

All models

Not Required

3

30” (750 mm) to 36” (900 mm) 

IM-1530

Not Required

4

Less than 30” (750 mm)

Not Required

Not Required

NOTES:

1. Infiltrator tank models include: IM-540, IM-1060, and IM-1530.

 2. Water height corresponds to seasonal high groundwater elevation or perched 

water elevation measured from bottom-of-tank elevation.

3. Minimum 6 inches (150 mm) soil cover backfill is required.

4.  IM-Series tanks shall not be installed where the water level outside the tank 

exceeds the height of the outlet pipe saddle. 

Figure 2:  Buoyancy Control Parameters for Table 1

Figure 1:  Assessing Water Elevation

Parameter I

Water Height

Above Tank Bottom  

Parameter II 

Depth Of Soil Cover Above Top Of Tank

 

NO BUOYANCY CONTROL IS REQUIRED IF THERE IS AT LEAST 

12 INCHES (300 MM) OF SOIL COVER ABOVE THE TANK TOP.

Maximum Allowable Water Elevation

Outside of the Tank Corresponds to 

Outlet Pipe Saddle Invert 

Tank Bottom

6” (150 mm) min – 48” (1,200 mm) max.

13” (330 mm)

Seasonal High

Groundwater 43”

(1,075 mm) max.

Above Tank Bottom 

Depth of Soil Cover Above Tank Top 

Top Of Tank

Contact Infiltrator Water Technologies’ Technical Services Department for assistance at 1-800-221-4436.

Summary of Contents for IM -Series

Page 1: ...gh elevation of the main water table The vertical position of the tank must account for both the seasonal high groundwater table and any existing or future perched water table condition Verify that the subsurface water elevation will not exceed the height of the outlet pipe saddle of the tank as shown in Figure 1 and described in Table 1 Table 1 Instructions 1 In the left hand column of Table 1 lo...

Page 2: ... outside the tank and above the tank bottom and corresponding soil cover conditions All Infiltrator strapping and fastening recommendations apply for custom designed buoyancy control methods Contact Infiltrator s Technical Services Department with any questions regarding supplemental force requirements Table 2 Buoyancy Control Method Selection Tank Model Parameter I Water height above tank bottom ...

Page 3: ...requirements for use as buoyancy control see Table 2 and the Supplemental Force section of Step 2 for more information Helical Anchors Chance No Wrench Screw Anchors with a 6 inch 150 mm diameter flight Class 7 or equal These anchors rely on the shear strength of the soil combined with the weight of the soil above the anchor flight to provide holding strength Proper installation is to 4 feet 1 2 m...

Page 4: ...uoyancy control methods described herein are recommendations only consult a professional engineer for customized designs if desired Parts and Supplies The parts and supplies necessary are to be purchased separately from the tank All parts and supplies are either commercially available or available through Infiltrator s network of tank distributors Some parts may require fabrication on site using c...

Reviews: