INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

SE18M24

1

Valve actuator for 0(2)...10 V control

SE18M24 is a valve actuator designed for control of AB Industrietechnik 
valves. The actuator has automatic self stroke adjustment and can be 
operated manually.

Technical data

Supply voltage 

 

24 V AC ±15 %, 50/60 Hz 

 

 

or 24 V DC ±15 % 

Control signal 

 

0(2)...10 V DC 

Max. power consumption   8.6 W / 22.4 VA 
Stroke 

 

10...52 mm 

Stroke time 

 

1,5 s/mm 

Force 

 

1800 N 

Ambient temperature 

0...50°C 

Storage temperature 

-40...80°C 

Ambient humidity   

10...90 % RH 

Dimensions (WxHxD) 

198 x 309 x 133 mm 

Protection class   

IP54

Installation

If the valve stem lock and valve throat adaptor are not already mounted

on the valve, mount them. Pull the valve stem out as far as possible.

Remove the screws (hex key 6 mm) and clamp from the actuator yoke.

Depress the spring-loaded tab on the drive rod coupling device and fit the

valve stem into the coupling.

Release the tab to connect the valve to the actuator. The position of the

yoke on the valve stem adaptor must be adjusted so that the clamp screw

holes line up with the groove in the valve throat adaptor. If the drive rod

needs to be moved in or out for this, depress the central button of the

control knob and turn it clockwise to extend the drive rod and counterclock-

wise to retract it (see Manual override). Mount the screws and the

clamp. Tighten the screws until the actuator is firmly attached.

Disassembly takes place in reverse order.

Mounting positions

90º

90º

Wiring

24 V AC/DC 

1

2

3

4

5

1

2

3

4

5

6

Ov

er

ride 

in

pu

t

Y    0(2)...10 V DC

Control signal from 

controller 

U    0...10 V DC

Measuring voltage 

for position indication 

Signal neutral

Y

U

B

M

G0

G

Stroke and endpoint calibration

Stroke and endpoint calibration is not necessary due to a construction 
utilizing endpoint stops. When the valve reaches the endpoint, a force is 

generated. Once the force of the actuator reaches a predefined level, the 

limit switch automatically halts the drive motor.

Override

Activation of the override input will force the valve to the maximum 
open position.

Manual override

To manually set the valve position, first depress the central part of the 
knob, until it clicks and remains depressed (1 in the figure). Then the 

valve position can be changed manually by turning the knob (2 in the 

figure). When the knob is turned clockwise, the drive rod is pushed 

outwards and when the knob is turned anti-clockwise, the drive rod is 
pulled inwards. 
To return to normal operation, set the knob so that it is in line with the 
text ”Auto” on the cover. Then depress the outer parts of the knob (3 

in the figure). The central depressed part will pop out, and the actua

-

tor will return to normal operation.
Note: After any manual operation the actuator will always run through 
a zero point calibration.

DIP switches

There are six DIP switches for setting different functions. Follow the 
table below for setting the DIP switches. 
Adjusted settings will be valid only after the next power-on.

1 (On)

0 (Off)

SW1

Spindle down when the 
valve is closed

Spindle up when the valve is 
closed (FS=factory setting)

SW2

LOG

LIN (FS)

SW3

Y = 2...10 V DC

Y = 0...10 V DC (FS)

SW4

Reverse operation

Direct operation (FS)

SW5

Y signal split in accordance 
with the setting of SW6

No split function (FS)

SW6

5(6)...10 V = 0...100 %

0(2)...5(6) V = 0...100 % (FS)

SE18M24

 

11921C JAN 18

EN

Summary of Contents for SE18M24

Page 1: ...2 10 V DC Control signal from controller U 0 10 V DC Measuring voltage for position indication Signal neutral Y U B M G0 G Stroke and endpoint calibration Stroke and endpoint calibration is not necessary due to a construction utilizing endpoint stops When the valve reaches the endpoint a force is generated Once the force of the actuator reaches a predefined level the limit switch automatically hal...

Page 2: ... valve position For cooling valves the blue marker should be in the completely open valve position and the red marker in the completely closed valve position EMC emissions immunity standards This product conforms to the requirements of the EMC Directive 2004 108 EC through product standards EN 60730 1 2000 and EN 60730 2 14 1997 RoHS This product conforms with the Directive 2011 65 EU of the Europ...

Page 3: ...unzioni Per la configurazione degli interruttori DIP seguire la tabella riportata di seguito Le nuove regolazioni delle impostazioni saranno valide a partire dalla suc cessiva accensione 1 On 0 Off SW1 Perno in basso con valvola chiusa Perno in alto con valvola chiusa FS impostazione di fabbrica SW2 LOG LIN FS SW3 Y 2 10 V DC Y 0 10 V DC FS SW4 Funzionamento inverso Funzionamento diretto FS SW5 Se...

Page 4: ...nnes AB Industri etechnik L ajustement de la course est automatique Le moteur dispose d une commande manuelle Caractéristiques techniques Tension d alimentation 24 V AC 15 50 60 Hz ou 24 V DC 15 Signal de commande 0 2 10 V DC Max puissance consommée 8 6 W 22 4 VA Course 10 52 mm Temps de course 1 5 s mm Force 1800 N Température ambiante 0 50ºC Température de stockage 40 80 C Humidité ambiante 10 9...

Page 5: ...re borne 2 SW3 doit être réglé sur On 2 10 V DC Le signal de commande 4 20 mA est alors converti en un signal 2 10 V DC SW4 Course directe inversée On Action inversée L actionneur ferme la vanne quand le signal de commande augmente Off Fonctionnement direct L actionneur ouvre la vanne quand le signal de commande augmente SW5 Fonction split On Fonction split active Deux actionneurs peuvent partager...

Page 6: ... erfolgt in umgekehrter Reihenfolge Einbaulagen 90º 90º Anschluss 24 V AC DC 1 2 3 4 5 1 2 3 4 5 6 Override input Y 0 2 10 V DC Control signal from controller U 0 10 V DC Measuring voltage for position indication Signal neutral Y U B M G0 G Hubweg und Enpunktkalibrierung Eine Hubweg und Endlagenkalibrierung wird nicht benötigt da bei Erreichen der Endlage eine Stellkraft generiert wird Erreicht di...

Page 7: ...3 On LEDs Der Stellantrieb ist mit einer roten und einer grünen LED ausge stattet die Folgendes anzeigen Anzeige Stetiges grünes Licht Stellantrieb funktioniert fehlerfrei Grünes schnell blinkendes Licht Testlauf Grünes langsam blinkendes Licht Einstellungen während des Testlaufs geändert Die neuen Einstellungen sind ab dem nächsten Einschalten gültig Stetiges rotes und grünes Licht Endlage erreic...

Reviews: