INSTRUCTION
i
Read this instruction before installation
and wiring of the product
SE18M24
1
Valve actuator for 0(2)...10 V control
SE18M24 is a valve actuator designed for control of AB Industrietechnik
valves. The actuator has automatic self stroke adjustment and can be
operated manually.
Technical data
Supply voltage
24 V AC ±15 %, 50/60 Hz
or 24 V DC ±15 %
Control signal
0(2)...10 V DC
Max. power consumption 8.6 W / 22.4 VA
Stroke
10...52 mm
Stroke time
1,5 s/mm
Force
1800 N
Ambient temperature
0...50°C
Storage temperature
-40...80°C
Ambient humidity
10...90 % RH
Dimensions (WxHxD)
198 x 309 x 133 mm
Protection class
IP54
Installation
If the valve stem lock and valve throat adaptor are not already mounted
on the valve, mount them. Pull the valve stem out as far as possible.
Remove the screws (hex key 6 mm) and clamp from the actuator yoke.
Depress the spring-loaded tab on the drive rod coupling device and fit the
valve stem into the coupling.
Release the tab to connect the valve to the actuator. The position of the
yoke on the valve stem adaptor must be adjusted so that the clamp screw
holes line up with the groove in the valve throat adaptor. If the drive rod
needs to be moved in or out for this, depress the central button of the
control knob and turn it clockwise to extend the drive rod and counterclock-
wise to retract it (see Manual override). Mount the screws and the
clamp. Tighten the screws until the actuator is firmly attached.
Disassembly takes place in reverse order.
Mounting positions
90º
90º
Wiring
24 V AC/DC
1
2
3
4
5
1
2
3
4
5
6
Ov
er
ride
in
pu
t
Y 0(2)...10 V DC
Control signal from
controller
U 0...10 V DC
Measuring voltage
for position indication
Signal neutral
Y
U
B
M
G0
G
Stroke and endpoint calibration
Stroke and endpoint calibration is not necessary due to a construction
utilizing endpoint stops. When the valve reaches the endpoint, a force is
generated. Once the force of the actuator reaches a predefined level, the
limit switch automatically halts the drive motor.
Override
Activation of the override input will force the valve to the maximum
open position.
Manual override
To manually set the valve position, first depress the central part of the
knob, until it clicks and remains depressed (1 in the figure). Then the
valve position can be changed manually by turning the knob (2 in the
figure). When the knob is turned clockwise, the drive rod is pushed
outwards and when the knob is turned anti-clockwise, the drive rod is
pulled inwards.
To return to normal operation, set the knob so that it is in line with the
text ”Auto” on the cover. Then depress the outer parts of the knob (3
in the figure). The central depressed part will pop out, and the actua
-
tor will return to normal operation.
Note: After any manual operation the actuator will always run through
a zero point calibration.
DIP switches
There are six DIP switches for setting different functions. Follow the
table below for setting the DIP switches.
Adjusted settings will be valid only after the next power-on.
1 (On)
0 (Off)
SW1
Spindle down when the
valve is closed
Spindle up when the valve is
closed (FS=factory setting)
SW2
LOG
LIN (FS)
SW3
Y = 2...10 V DC
Y = 0...10 V DC (FS)
SW4
Reverse operation
Direct operation (FS)
SW5
Y signal split in accordance
with the setting of SW6
No split function (FS)
SW6
5(6)...10 V = 0...100 %
0(2)...5(6) V = 0...100 % (FS)
SE18M24
11921C JAN 18
EN