Ref. 006001001300
Rev. 0: 30-08-2019
RIGHT ZONE
RIGHT ZONE.
The right zone configures the outputs. If the switch is set to “ON” the Q0.X will
have the behaviour of a digital output. If it is set to “OFF” it will be analog. There is also a
switch for switching between Half and Full Duplex. It is “ON” for Half Duplex and “OFF” for Full
Duplex.
8.2
RS- 485 Switch configuration
RS-485 TOP ZONE:
In order to enable the RS-485 protocol the TOP ZONE
must be configured as it is shown in the table.
Although the switch serigraphy is only referenced to RS-485 it is also the
for the RS-232.
Having this setup, the I0.3 & I0.2 are disabled
RS-485 LEFT ZONE
: In order to enable the RS-485 communication
protocol it is necessary that the switches of the left zone are
configured as it is showed in the table.
The ones marked with “-“ mean that they don’t affect the RS-485
communication protocol
RIGHT ZONE
SWITCH
OFF
ON
H/F
Full Duplex
Half Duplex
Q0.6
ANALOG (A0.6)
DIGITAL (Q0.6)
Q0.5
ANALOG (A0.5)
DIGITAL (Q0.5)
Q0.4
ANALOG (A0.4)
DIGITAL (Q0.4)
Q0.3
ANALOG (A0.3)
DIGITAL (Q0.3)
Q0.2
ANALOG (A0.2)
DIGITAL (Q0.2)
Q0.1
ANALOG (A0.1)
DIGITAL (Q0.1)
Q0.0
ANALOG (A0.0)
DIGITAL (Q0.0)
TOP ZONE
SWITCH
MODE
I0.3
OFF
RS485 HS
ON
I0.2
OFF
RS485 HS
ON
LEFT ZONE
SWITCH CONFIGURATION
SWITCH
MODE
DE-RS485
ON
D10/A0.2-Q0.2
OFF
RE-RS485
ON
D11/A0.1-Q0.1
OFF
SDA-D2/I0.0
-
SCL-D3/Q0.6
-
Summary of Contents for PLC Arduino ARDBOX
Page 31: ...Ref 006001001300 Rev 0 30 08 2019 Digital Output Turn off PWM Waveform Analog Out Turn on...
Page 33: ...Ref 006001001300 Rev 0 30 08 2019 14 Typical Connections...
Page 34: ...Ref 006001001300 Rev 0 30 08 2019...
Page 35: ...Ref 006001001300 Rev 0 30 08 2019...
Page 37: ...Ref 006001001300 Rev 0 30 08 2019 16 ARDBOX Family Dimensions 45mm width 17 DIN rail mounting...