background image

Syncro_View_AUS_v2.0.docx 

Page 6 of 12 

5

 

Connecting to the circuit board  

 
All connections for field wiring are to a single row of terminals along the bottom of the circuit board.  
Shielded fire alarm cable such as FP200 and metal cable glands must be used for all connections to the unit. The 

resistance of any core of the data cable must not exceed 25 ohms. The shield of the cable must be bonded 

securely to the enclosure via the metal gland.  
Wiring should enter the enclosure at the top or back of the unit using the knockouts provided and be formed 

tidily to the appropriate terminals.  
Terminals are capable of accepting wires of up to 2.5mm

2

.  

Wiring must not go across the front of the circuit board. If cable entries need to be in positions other than at the 

knockouts provided, wiring must be fed well away from the surface of the circuit board.  

6

 

Power and data connections  

 
Each unit requires two cores for power and two cores for data transmission to and from the control panel. A four 

core cable may be used for these connections. All of these connections are polarity conscious and care should be 

taken to match the polarity with the corresponding terminals at the control panel. Mains powered versions require 

only a two core cable to the control panel and a local mains supply.  

6.1

 

Data Termination  

 
Up to 15 units can be connected to a Syncro control panel. In and out terminals for data and 24V DC are provided 

on each unit.  
All units are supplied with a push on jumper fitted at position J3 on the left hand side of the PCB. This jumper 

connects a terminating resistor which needs to be in place at the last unit on the data line. If more than one unit 

is to be fitted, then the jumpers must be removed from all units except the last one.  
If there is only one unit fitted then the jumper should be left in place. The COMMS LED will flash quickly while 

the unit is communicating correctly with the control panel and will be off if the unit is disconnected or connected 

incorrectly. 
 

6.2

 

Power Supply 

 

Mains Connection 

Select the required operating voltage (115/230) via the selector switch adjacent to the 

mains input. The mains is connected to the PSU via a fused terminal block marked with 

live, neutral and earth symbols. It is imperative that the equipment is soundly earthed 

and this connection should be made and checked first. 
Following connection of the live and neutral cables and with no other connections made, 

the unit should be powered and the battery output measured at around 28 volts DC (For 

nominal 24V setting) or 14 volts DC (for nominal 12V setting.) 
 

Load Connection 

A maximum load of 750mA can be drawn with either 24V or 12V settings. (The 

recommended maximum continuous load is 500mA.) Terminals are provided for 

connection to the load and are  and -. The voltage at these terminals under 

normal conditions (i.e. off load) should be around 28.5 to 29 volts DC (for nominal 24V 

setting) or 14 to 14.5 volts (for nominal 12V setting.) With the mains power off, connect 

the load cables. 
Double check the load connection for correct polarity before switching on mains. After 

switching on mains check the voltage at the load for correct polarity. 
Do not connect or disconnect the wiring to the load terminals with mains or battery power 

on. 

Summary of Contents for SYNCRO

Page 1: ...Australia Version 2 March 2016 Product Manual Analogue Addressable Syncro View Serial LCD Repeater Panel SYNCRO ...

Page 2: ... is connected Therefore silencing the buzzer at the host panel will also silence the buzzer on the Syncro View repeater s connected to that panel 2 Safety and mounting 2 1 Safety Suppliers of articles for use at work are required to ensure as reasonably as is practical that the article will be safe and without risk to health when properly used An article is not regarded as properly used if it is u...

Page 3: ...mount the enclosure in all three mounting positions Suitable fixings should be used at all fixing points such that the unit is securely mounted and is not liable to move once fixed Units should not be mounted in another enclosure or near sources of excessive heat Cables should be connected using suitable cable glands If additional cable entry points are required all swarf and debris caused by dril...

Page 4: ...nt Mains powered models only 200 millivolts Battery type Yuasa NP Mains powered models only Two 12 Volt 1 9Ah sealed lead acid in series Battery charge voltage Mains powered models only 27 6VDC nominal Battery charge current Mains powered models only 0 2A maximum Battery fuse Mains powered models only 200 milliamp 20mm glass Maximum current draw from batteries Mains powered models only 0 095 Amps ...

Page 5: ...Syncro_View_AUS_v2 0 docx Page 5 of 12 4 Syncro View fascia Models with enable controls keyswitch Models without enable controls keyswitch ...

Page 6: ... of the PCB This jumper connects a terminating resistor which needs to be in place at the last unit on the data line If more than one unit is to be fitted then the jumpers must be removed from all units except the last one If there is only one unit fitted then the jumper should be left in place The COMMS LED will flash quickly while the unit is communicating correctly with the control panel and wi...

Page 7: ... used to switch other voltages or signals 750mA typical wiring connections always read safety notice at front of manual before making any connections 7 Addressing the units To enable the control panel to know whether any units that should be connected have been disconnected and indicate a fault condition each unit must be allocated an address The address switch should never be set with all switche...

Page 8: ...affect its proper operation a watchdog W DOG LED indicator is latched on and a fault condition signalled to the control panel If a processor re start has occurred this latched fault condition will need to do a reset by pressing the W DOG RESET button on the bottom of the PCB A switch is also provided to manually re start the processor PROC RESET This switch can be used while the units are connecte...

Page 9: ...tion utility Click on the site name in the left hand window pane to show the option to add panels or repeaters to the system If no panels are already added to the configuration then first add the type of panel required by double clicking on it in the lower panel Add a Syncro view repeater by double click on the View Repeater Icon Double click on the panel to which the View repeater is to be connec...

Page 10: ...ame location and an address on the serial bus This address should be different for each Syncro View added and different to any other I O boards that may exist on the serial bus Once the configuration file has been loaded into the panel the panel will now expect to see a Syncro View at the address allocated to it and will show a fault condition if the Syncro View is not fitted or is removed ...

Page 11: ...Page 11 of 12 11 Revision Details Revision Number Reason Date of issue v1 0 Initial Release V2 0 Change of Incite Sydney address Add power supply details into section 6 and corrected PO connection on section 9 drawing 29 03 2016 ...

Page 12: ...cal support support incitefire com au Melbourne Address Unit 120 45 Gilby Road MT WAVERLEY VIC 3149 Phone 03 9544 2211 Fax 03 9544 2212 Email salesvic incitefire com au Brisbane Address 25 Jeays Street BOWEN HILLS QLD 4006 Phone 07 3252 5366 Fax 07 3252 4099 Email salesqld incitefire com au Perth Address 19 Halley Road BALCATTA WA 6021 Phone 08 9349 2972 Email saleswa incitefire com au ...

Reviews: