FIREscape System Installation Manual
Page 18 of 56
Voltage for device connected
to PRG card
MF2
0.3 (automatic fuse) 4
X3
Voltage for EL-EXP card
MF3
0.3 (automatic fuse) -
X4
NOTE: The total maximum load for outputs F3+F4 is 0.6 A.
8.2
Relay Outputs
The control panel has 2 relay outputs. These can be configured as normally open (N/O) or normally closed
(N/C). The outputs are rated at:
Output
Action
Rating [Amps]
Points
Connector
EXT1
Relay, C
1
14
X1
EXT1
Relay, NC
1
15
X1
EXT1
Relay, NO
1
16
X1
FAIL
Relay, C
1
17
X1
FAIL
Relay, NC
1
18
X1
FAIL
Relay, NO
1
19
X1
8.3
LEDs
The LEDs on the motherboard indicate functions and serial communication. RX indicates serial communication
reception (red)
TX indicates serial communication transmission (green)
CPN (green), TX = Data sent from CPN port (NL-KLG)
PRN (red), TX = Data sent from PRN port
PRG (red), RX = Data received to the PRG port from a device
PRG (green), TX = Data sent from the PRG port from a device
FAIL (red) = Software fault, program execution termination
PR OFF (yellow) = Write-protected configuration memory unlocked for editing.
Summary of Contents for FIREscape
Page 1: ...Emergency Lighting System INSTALLATION MANUAL ...
Page 22: ...FIREscape System Installation Manual Page 24 of 56 Figure 6 An example of a spur arrangement ...
Page 37: ...FIREscape System Installation Manual Page 39 of 56 Figure 20 EL EXP Connection ...
Page 47: ...FIREscape System Installation Manual Page 49 of 56 Minimum Operating Voltage 7 5 V Figure 28 ...
Page 48: ...Page 50 of 56 FIREscape System Installation Manual Minimum Operating Voltage 8 5 V Figure 29 ...
Page 50: ...Page 52 of 56 FIREscape System Installation Manual Minimum Operating Voltage 7 5 V Figure 31 ...
Page 51: ...FIREscape System Installation Manual Page 53 of 56 Minimum Operating Voltage 8 5 V Figure 32 ...