Imron Corporation SI-16 Installation And Specification Download Page 1

 

 

Imron Corporation   15375 Barranca Pkwy, Suite B-106

Irvine, CA 92618  Phone 949-341-0947  Fax 949-341-0949

 

 

INTEGRATED SYSTEM 2000  

 

SI-16 INPUT PROCESSOR

 

System Control Processor

 

Installation and Specification 

 

1. General:

 

 

The  SI-16  sub-controller  provides  sensor  interface  and  output  controls  for  system  integrators  in 

security/access control and other application. The controller has 16 input channels for supervised contact 

monitoring and 2 form-C contacts for load switching. In addition, 2 digital inputs may be used for tamper 

and UPS status monitoring.  The sub-controller requires either 12Vdc or 12Vac for power. 

 

 

 

Summary of Contents for SI-16

Page 1: ... 1 General The SI 16 sub controller provides sensor interface and output controls for system integrators in security access control and other application The controller has 16 input channels for supervised contact monitoring and 2 form C contacts for load switching In addition 2 digital inputs may be used for tamper and UPS status monitoring The sub controller requires either 12Vdc or 12Vac for po...

Page 2: ...o the unit as possible Connect power with minimum of 18AWG wires Observe POLARITY for 12Vdc application 3 Communication Wiring The SI 16 communicates to host via a RS 485 interface which may be configured for either 2 wire or 4 wire operation The interface allows multi drop communication on a single bus of up to 4 000 feet 1 200 m Use twisted pair s minimum 24 AWG with shield for the communication...

Page 3: ...open or normally closed contacts Input CT and input BA are typically used for monitoring cabinet tamper and power failure respectively These two inputs are for contact closure monitoring only and do not use EOL resistor s 5 Relay Outputs The following show typical use of the relay outputs DC source is recommended whenever it is possible Transient clamping must be provided to protect the contact an...

Page 4: ...S 5 OFF OFF ON ON OFF ADDRESS 6 OFF OFF ON ON ON ADDRESS 7 OFF ON OFF OFF OFF ADDRESS 8 OFF ON OFF OFF ON ADDRESS 9 OFF ON OFF ON OFF ADDRESS 10 OFF ON OFF ON ON ADDRESS 11 OFF ON ON OFF OFF ADDRESS 12 OFF ON ON OFF ON ADDRESS 13 OFF ON ON ON OFF ADDRESS 14 OFF ON ON ON ON ADDRESS 15 ON OFF OFF OFF OFF ADDRESS 16 ON OFF OFF OFF ON ADDRESS 17 ON OFF OFF ON OFF ADDRESS 18 ON OFF OFF ON ON ADDRESS 19...

Page 5: ...n supervised Wire requirement Power 1 twisted pair 18 AWG RS 485 24AWG 4 000ft 1 200m max twisted pair s with shield Alarm input 1 twisted pair 30 ohms max Output As required for the load Environmental Temperature 0 to 70 C operating 55 to 85 C storage Humidity 0 to 95 RHNC Mechanical Dimension 6 in 152mm W x 8 in 203mm L x 1 in 25mm H Weight 10 oz 290 gm nominal This device complies with part 15 ...

Page 6: ...horize any agent or representative to make any other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returned units are repaired or replaced from a stock of reconditioned units Returns must be accompanied by a return authorization number RMA obtained from customer service and prepaid postage and ins...