2.6 INFORMATION MENU.
By pressing the button “
“, the “Information menu” is activated
for at least 1 second, displaying some boiler operating parameters.
To scroll through the various parameters, press the buttons “DHW
regulation” “
“.
With the menu active on the indicator (19) the parameter via the
letter “d” plus the number of the parameter that is being displayed
will alternately show.
To view the parameter value, select it by pressing the button
.
Press “
” or wait 15 minutes to go back to the previous
screen or exit the menu.
Parameter ID
Description
d 0.0
Not used
d 0.1
Displays the flame signal (uA)
d 0.2
Displays the primary heat exchanger output instant heating flow temperature
d 0.3
Displays the instant output temperature from the DHW exchanger
d 0.4
Displays the values set for central heating set
d 0.5
Displays the values set for DHW set
d 0.6
Displays the external environment temperature (if optional external probe present)
If the temperature is below zero, the value is displayed flashing.
d 0.7
Displays the temperature of the inlet DHW (with optional DHW inlet probe present)
d 0.8
Displays the system return water temperature
d 0.9
Displays the list of the last eight anomalies.
(to scroll the list press the “central heating temperature regulation” buttons (6 and 7))
d 1.0
Anomaly list reset. Once “d 1.0” is displayed, press the Reset button for at least 3 seconds; deletion is confirmed via the “88”
symbols flashing for two seconds
d 1.1
Not used
d 1.2
Displays the pump operating speed
d 1.3
Not used
d 1.4
Displays the pump flow rate (lh/100)
d 1.5
Displays the fan operating speed (rpm/100)
d 1.6
Displays the temperature read on the flue probe
d 1.7
Displays the calculated flow temperature
d 1.8
At the end of the screed heater function, displays for how many hours the flow temperature remained at “Top set”
d 1.9
Toggles between the safety software version and the functional software version
d 2.0
Displays the flow temperature of zone two (optional)
d 2.1
Displays the flow temperature of zone three (optional)
d 2.2
Not used