31
INS
TALLER
US
ER
MAINTEN
AN
CE TECHNI
CI
AN
3.9 ADJUSTING THE AIR GAS RATIO
During complete calibration (par. 3.8), you can
modify the values of the air - gas ratio.
To have an exact value of CO
2
in the flue, the
technician must insert the sampling probe to the
bottom of the sample point, then check that the
CO
2
value is that specified in the table in (Par.
3.23), (with maximum tolerance equal to
±
0.2
%). If otherwise, change the value as described
hereunder:
- during calibration, when the frame of the
flame presence starts flashing (indicating the
correct acquisition of the parameters) it is
possible to alter the CO
2
value by pressing the
“Reset” button. At this stage the display features
flashing icons: “summer”, “winter”, “stand-by”,
“flame presence”, “external connected devices
presence” and the operating temperature is
displayed, alternated with the combustion
setting.
- To increase the combustion setting, press the
“Stand-by” button; to decrease it, press the
“Info” button. As the combustion setting in-
creases, the CO
2
value decreases and vice-versa.
- Once the parameter has been altered wait for
the value to be saved (displayed via the frame
of the flame presence symbol flashing).
- To confirm the set value press the “Reset” but-
ton.
3.10 FAST CALIBRATION.
This function allows you to calibrate the boiler
automatically without requiring or giving the
possibility to alter the parameters. Typically
“fast calibration” is used after having set the type
of flue in menu “F”, which once altered causes
anomaly “72”.
N.B.:
before performing a quick calibration,
ensure that all the requirements indicated in
paragraphs 1.21 and 1.22 have been fulfilled.
N.B.:
to access this function it is crucial that
there are no active requests for central heating
or DHW production.
In the event of anomaly “62” or “72” (see parag.
2.5) the boiler cancels any requests by itself.
The energy produced is dissipated via the heat-
ing circuit; alternatively, the energy can be
released from the DHW circuit by opening any
hot water tap.
Caution:
in this case the only active temperature
control is the flow probe that limits the maximum
temperature exiting the boiler at 90°C, therefore
be careful not to get burned.
In order to access the fast calibration stage, set
the DHW selector in the “6 o' clock” position and
the heating selector in the “9 o' clock” position,
(Fig. 3-10) and press the “Reset” button for about
8 seconds until the “chimney sweep” function is
activated; then press the “info” button within
3 seconds.
3-
9
Once the function is active, the boiler sequential-
ly carries out the procedures required to calibrate
the appliance with the nominal, intermediate and
minimum heat output values.
At this stage the display features flashing icons:
“summer”, “winter”, “stand-by”, “external probe”,
“solar probe” and the operating temperature is
displayed, alternated with the current operating
heat output.
The calibration stages (nominal, intermediate
and minimum) progress automatically and you
must wait until calibration is complete.
3.11 FLUE TEST.
To define the value to set in the ”flue length”
“F0” parameter, detect the parameters during
the “flue test”.
Attention:
Before performing the test, ensure
that the condensate drain trap has been filled
correctly and check that there are no obstructions
in the air intake circuit and flue exhaust.
Once the test has been carried out properly, note
the detected value in the relevant table, in order
to have it available for future checks.
To activate this mode, the boiler must be in
“stand-by” mode, which is visible when the
(
) symbol appears.
N.B.:
if the boiler is connected to the CAR
V2
the
“stand-by” function can only be activated via the
remote control panel.
3-1
0
3-11
To activate the function, press the “Reset” (2) and
“on/off” (6) buttons simultaneously until func-
tion activation, which is displayed by indicating
the fan operation speed (in hundreds of revs) and
ignition of the flashing “D.H.W.” (8) and central
heating symbols.
The appliance remains in this mode for a maxi-
mum period of 15 minutes, keeping the fan speed
constant.
This function ends once 15 minutes have elapsed,
or by disconnecting supply voltage to the boiler,
or by pressing the “on/off” (6) button for ap-
proximately 8 seconds.
Check the
Δ
P between the two pressure test
outlets (Fig. 1-29 Ref. 16) and set parameter F0
according to the values shown in the tables below:
Victrix Maior 28 TT 1 ErP
Parameter F0
Pressure
0
<
175 Pa
1
176
÷
205 Pa
2
206
÷
250 Pa
Detected Value
(Upon first check)
Victrix Maior 35 TT 1 ErP
Parameter F0
Pressure
0
<
180 Pa
1
181
÷
230 Pa
2
231
÷
260 Pa
Detected Value
(Upon first check)
N.B.:
examinations are carried out by sealing the
holes provided to analyse the flues, making them
pneumatically sealed.
Attention:
in the event of finding greater values
compared to those indicated in the previous
table, do not alter parameter “F0”.
Attention:
should there be a boiler malfunction,
you can carry out a flue test to check that there
are no obstructions in the flue system. Different
values to those indicated in the previous tables
indicate a flue system malfunction, especially
a flue system with excessive load losses or ob-
structed system.
3-12
Summary of Contents for Victrix Maior 28 TT 1 ErP
Page 1: ...VICTRIX MAIOR 28 35 TT 1 ERP IE Instruction and recommendation booklet 1 038659ENG...
Page 2: ......
Page 49: ...49...
Page 50: ...50...
Page 51: ...51...