background image

15 

4

3

2

1

5

6

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

3.4  CONVERTING THE BOILER TO 

OTHER TYPES OF GAS.

If the appliance needs to be converted to a 

different gas type to that specified on the data 

plate, request the relative conversion kit for quick 

and easy conversion.

Boiler conversion must be carried out by a 

qualified technician (e.g. Immergas After-Sales 

Technical Assistance Service).

To convert to another type of gas the following 

operations are required:

- disconnect the appliance;
-  replace the main burner injectors, making sure 

to insert the special seal rings supplied in the 

kit, between the gas manifold and the injectors;

- move jumper 16 (Fig. 3-3) to the correct 

position for the type of gas in use (Methane or 

L.P.G.);

-  to access adjustments on the circuit board, the 

cover must be removed from the dashboard by 

taking out the rear fixing screws;

- re-power the appliance;
- adjust the maximum heat power of the boiler;
- adjust the minimum heat power of the boiler;
- adjust (if necessary) the heating power;
- seal the gas flow rate regulation devices (if 

settings are modified);

- after completing the conversion, apply the 

sticker, contained in the conversion kit, near 

the data-plate. Using an indelible marker pen, 

cancel the data relative to the old type of gas.

These adjustments must be made based on 

the type of gas used, following the indications 

provided in the tables (Par. 3.16).

3.5  CHECKS FOLLOWING CONVERSION 

TO ANOTHER TYPE OF GAS.

After making sure that conversion was carried 

out with a nozzle of suitable diameter for the 

type of gas used and the settings are made at the 

correct pressure, check that:

- there is no flame in the combustion chamber;
-  the burner flame is not too high or low and that 

it is stable (does not detach from burner);

- the pressure testers used for calibration are 

perfectly closed and there are no leaks from 

the gas circuit.

N.B.: 

All boiler adjustment operations must 

be carried out by a qualified technician (e.g. 

Immergas After-Sales Technical Assistance 

Service). 

Burner adjustment must be carried out using a 

"U" or digital pressure gauge connected to the 

gas valve outlet pressure point (Part. 4 Fig. 3-3), 

keeping to the pressure value provided in the 

tables (Par. 3.16) according to the type of gas for 

which the boiler is prepared.

Fig. 3-3

P.C.B.

SIT 845 GAS Valve

  10  -  Phase fuse 3.15AF

  11  -  Neutral fuse 3.15AF

  12  -  Main switch

 13 -  Domestic hot water temperature trimmer

  14  -  RS232 computer interface

  15  -  Central heating temperature trimmer

  16  -  METHANE L.P.G. gas type selector

3.6  POSSIBLE ADJUSTMENTS OF THE 

GAS VALVE.

• Adjustment of boiler nominal heat output (see 

previous figure). 

- Turn the domestic hot water temperature 

selector (10 Fig. 2-1) to maximum;

- open the domestic hot water cock in order to 

prevent modulation from starting up;

-  adjust the nominal boiler power from the brass 

nut (3), keeping to the maximum pressure 

values provided in the tables (Par. 3.16) 

depending on the type of gas; 

- by turning it clockwise the heating potential 

increases and by turning it anti-clockwise the 

heating potential decreases.

• Adjustment of minimum boiler heat output 

(Fig. 3-3). 

N.B.:

 only proceed after having calibrated the 

nominal pressure.
Adjustment of the minimum thermal input is 

obtained by operating on the cross plastic screws 

(2) on the gas valve maintaining the brass nut 

blocked (3);

-  disconnect the power supply to the modulating 

coil (just disconnect a faston); by turning the 

screw in a clockwise direction, the pressure 

increases, and counter-clockwise it decreases. 

On completion of calibration, re-apply the 

power supply to the modulating coil. The 

minimum boiler power must not be adjusted 

to a pressure value below the levels stated in the 

tables (Par. 3.16) depending on the type of gas. 

N.B.:

 to adjust the gas valve, remove the plastic 

cap (6); after the adjustment, put the cap back on.

Key:

  1 -  Coil

  2  -  Minimum power adjustment screw

  3  -  Maximum power adjustment nut

  4  -  Gas valve outlet pressure point

  5  -  Gas valve inlet pressure point

  6  -  Protection hood

Summary of Contents for NIKE MINI 28 KW SPECIAL

Page 1: ...NIKE MINI 28 KW SPECIAL Instruction and warning booklet IE 1 038788ENG ...

Page 2: ... technical information for installing Immergas boilers As for the other issues related to boiler installation e g safety in the work site environment protection injury prevention it is necessary to comply with the provisions specified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within th...

Page 3: ...al heating system pressure 12 2 9 System draining 12 2 10 Anti freeze protection 12 2 11 Case cleaning 12 2 12 Decommissioning 12 3 Boiler start up initial check 13 3 1 Hydraulic diagram 13 3 2 Wiring diagram 14 3 3 Troubleshooting 14 3 4 Converting the boiler to other types of gas 15 3 5 Checks following conversion to another type of gas 15 3 6 Possible adjustments of the gas valve 15 3 7 Program...

Page 4: ...ates the warranty Installation regulations theseboilerscannotbeinstalledinbedrooms studio flats and bathrooms They also cannot be installed in rooms with wood or solid fuel burning heat generators and in adjacent and communicating rooms Installation in places with a fire risk is prohibited for example garages closed parkingstalls gasappliancesandrelativeflue ducts flue exhaust pipes and combustion...

Page 5: ...e type used in the boiler which must comply with the regulations in force as insufficient levels can reduce generator output and cause malfunctions Ensure correct gas cock connection by following the mounting instructions illustrated in the figure The gas supply pipe must be suitably dimensioned according to current regulations in order to guarantee correct gas flow to the burnereveninconditionsof...

Page 6: ...ergas chrono thermostats are connected with 2 wires only Carefully read the user and assembly instructions contained in the accessory kit On Offdigitalchrono thermostat Thechrono thermostat allows set two room temperature value one for daytime comfort temperature and one for nighttime lower temperature set a weekly programme with four daily switch on and switch off times select the required operat...

Page 7: ... dangerous situations for the user The flue ducts must be connected to the chimney or flue in the same room in which the appliance is installed or at most in the adjoining room and must comply with the requirements indicated by the regulation 1 8 FLUES CHIMNEYS For the appliances with natural draught individual chimneys and branched flues can be used Individual chimneys The individual flues must b...

Page 8: ...supplyfailureandchecktherelative intervention time check activation of the main switch located upstream of the boiler The boiler must not be started up even if only one of the checks should be negative N B The preliminary boiler check must be carried out by a qualified technician The standard boiler warranty is valid from the date of inspection The test certificate and warranty is issued to the us...

Page 9: ...ety thermostat 6 Fumes hood 7 Delivery probe 8 Safety thermostat 9 System expansion vessel 10 Combustion chamber 11 Boiler circulator pump 12 3 bar safety valve 13 Automatic by pass 14 Three way valve motorised 15 System draining valve 16 Primary heat exchanger 17 Ignition and detection electrodes 18 Vent valve 19 DHW heat exchanger N B connection group optional ...

Page 10: ... other devices Never clean the appliance or connected parts with easily flammable substances Never leave containers or flammable substances in the same environment as the appliance It is prohibited and dangerous to obstruct the air intake even partially for the ventilation of the room in which the boiler is installed Due to the danger functioning is also prohibited in the same room as suction devi...

Page 11: ...and 7 flash at the same time 04 Parasite flame block LEDs 1 and 7 flash at the same time 20 Loss of remote control communication LEDs 2 and 3 flash alternately 31 Insufficient water circulation This occurs if there is overheating in the boiler due to insufficient water circulating in the primary circuit the causes can be low system circulation check that no shut off devices are closed on the heati...

Page 12: ...rmal pressure via the valve located at the bottom of the boiler Fig 2 2 N B close the valve after the operation If pressure values reach around 3 bar the safety valve may be activated In this case contact a professional technician for assistance In the event of frequent pressure drops contact qualified staff for assistance to eliminate the possible system leakage 2 9 SYSTEM DRAINING To drain the b...

Page 13: ...he appliance e g a draught gauge positioned at the exit of the appliance combustion products check that there is no backflow of combustion products into the room even during functioning of fans ensure activation of all adjustment devices seal the gas flow rate regulation devices if settings are modified check the production of domestic hot water check sealing efficiency of water circuits check ven...

Page 14: ...ect installation of the terminal Frequent interventions of the over heating safety thermostat It can depend on reduced water pressure in the boiler little circulation in the heating system the blocked pump or an anomaly of the boiler P C B Check on the pressure gauge that the system pressure is within established limits Check that radiator valves are not all closed The boiler produces condensate T...

Page 15: ...operations must be carried out by a qualified technician e g Immergas After Sales Technical Assistance Service Burner adjustment must be carried out using a U or digital pressure gauge connected to the gas valve outlet pressure point Part 4 Fig 3 3 keeping to the pressure value provided in the tables Par 3 16 according to the type of gas for which the boiler is prepared Fig 3 3 P C B SIT 845 GAS V...

Page 16: ... tables Heating output The boiler is produced and calibrated in the central heating phase at nominal output Permanent reduction of the timer The boiler has an electronic timing device that prevents the burner from igniting too often in the heating phase The boiler has a standard supply of a timer adjusted at 180 seconds Heating switch on timer continuous variation Flashing LED slow 30 seconds LED ...

Page 17: ...r with boiler in standby the function activates every 18 hours after the last boiler check power supply In case of functioning in domestic hot water mode the self check starts within 10 minutes after the end of the withdrawing in progress for duration of approx 10 seconds N B during self check the boiler remains off including signalling 3 14 YEARLY APPLIANCE CHECK AND MAINTENANCE The following che...

Page 18: ...panel 4 towards you taking care to remove the 2 fixing screws 5 3 16 HEAT OUTPUT N B gasflowratesrefertoheatingpowerbelowa temperature of 15 C and a pressure of 1013 mbar Burner pressure values refer to use of gas at 15 C METHANE G20 BUTANE G30 PROPANE G31 THERMAL POWER THERMAL POWER BURNER GAS FLOW RATE PRESS BURNER NOZZLES BURNER GAS FLOW RATE PRESS BURNER NOZZLES BURNER GAS FLOW RATE PRESS BURN...

Page 19: ...ic hot water circuit flow limiter at 2 bar l min 9 3 Domestic circuit min pressure dynamic bar 0 3 Domestic hot water circuit max working pressure bar 10 Minimum D H W flow rate l min 1 5 Specific flow rate T 30 C l min 12 8 Flow rate capacity in continuous duty T 30 C l min 13 2 Weight of full boiler kg 33 9 Weight of empty boiler kg 31 0 Electrical connection V Hz 230 50 Nominal absorption A 0 4...

Page 20: ...d Model Cod Md Model code Sr N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat input Pn min Minimum heat output Pn max Maximum heat output PMS Maximum system pressure PMW Maximum domestic hot water pressure D Specific flow rate TM Maximum operating te...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ... immergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038788ENG rev 002114 000 07 15 Inglese per IRLANDA IE ...

Reviews: