Illumra E3X-T02-U2W Installation Manual Download Page 1

Copyright © 2009 ILLUMRA. All rights reserved.      

Contact ILLUMRA:

     T: (80) 349-200     |     F: (80) 653-4257     |       [email protected]     |     www.ILLUMRA.com 

AHD025B

Installation Guide

E3X-T02-U2W

24VAC Thermostat

Overview

The 24VAC Thermostat provides digital temperature control of heating and cooling–with 

wireless communication to multiple ILLUMRA devices.  It is designed for use with most 

basic gas/electric furnace/air conditioning units, PTHP/PTAC Systems, 4-pipe, or 2-pipe 

fan coil systems.  Solid-state control outputs allow switching of electronic and relay loads 

of 1.5 amps.  This control operates from a single setpoint with automatic changeover 

between heating and cooling.  The fan cycles on/off with calls for heating or cooling or can 

operate continuously in either low, medium, or high speed.  The control can be placed in 

economy mode or off mode with 40° freeze protection.  Economy mode is enabled and 

disabled by one or more compatible transmitters.

Compatible Devices

Key Card Access Switch; E3T-C1AWH

Single Rocker Self-powered Wireless Light Switches; E3T-S1Axx

Dual Rocker Self-powered Wireless Light Switches; E3T-S2Axx

Dual Rocker Handheld Remote; E3T-S2Hxx

SLT Wireless Sensor; E3T-Rxx-2INBP

Self-powered Wireless Occupancy Sensor; E3T-Mxx-SB24

More transmitters available

Components Included

The following items are included with this product: 

A -- (1) ILLUMRA 24VAC Thermostat

B -- (2) Mounting Screws (6/32” x 3/4”)

C -- (1) Self Tapping Screw

D -- (1) Mounting Bracket

Optional Accessories

A -- Horizontal Mounting Plate (not included)

Tools Needed for Installation

Phillips Screwdriver

Electrical Tape

Wire Nuts

Programming the Thermostat

CAUTION:  ILLUMRA Relay Receivers are to be installed and/or used in compliance 

with relevant electrical codes and regulations.  If you are unsure about any portion of 

these instructions, please contact a qualified electrician.  These devices are intended for 

indoor use, for permanently installed fixtures, and for dry locations.

Connect the thermostat to a 24VAC power source for initial setup.  DO NOT 

CONNECT THE OTHER WIRES UNTIL THIS STEP IS COMPLETE.  PREVENT 

ALL OTHER WIRES FROM TOUCHING DURING THIS PROCESS TO 

AVOID DAMAGE TO THE THERMOSTAT.  DAMAGE DUE TO INCORRECT 

WIRING WILL VOID WARRANTY. 

 The programming mode has a time limit of 10 

minutes.  After 10 minutes, the thermostat will resume normal operation.  The default 

values mentioned throughout this section refer to factory programmed settings.  If the 

thermostat has been custom programmed, the defaults may not apply.

NOTE:    For programming large numbers of devices, an accessory is available to copy 

settings from one device to another.  Contact ILLUMRA for details.

Access Code 43:

Configuration Mode

Step 1:    Place thermostat into programming mode by pressing and holding the UP 

and DOWN arrows while sliding the °F/°C switch to the opposite side.  00 

will appear on the display.  Do not use the °F/°C switch again until done 

programming.

Step 2:    Press either the up or down arrow button to find the access code 43 then 

press the fan button.

Step 3:    Press either the up or down arrow button to scroll through the menu to 

reach the desired parameter (see below), then press the Fan button.

  Exit Menu (Ext):
  Equipment Type (E9P): Type of Equipment
    tHP - Default, Trane heat pump, type O reverse valve
    tAC - Trane AC with electric heat
    FHP - Friedrich heat pump, type B reverse valve
    FAC - Friedrich AC with electric heat
    gHP - GE heat pump, type B reverse valve
    gAC - GE AC with electric heat
    AHP - Amana heat pump, type B reverse valve
    AAC - Amana AC with electric heat
    FC - fan coil
  Reverse Valve Type (typ):  Selects the valve type
    O type - Default, energizes in calls for cooling
    B type - energizes in calls for heating
  Heat Pump or AC (Pt):
    HP - Default, 2 stage heat, single stage cool
      Y = compressor, W = 2nd stage heat
    AC - AC and electric heat
      Y = cool, W = heat
  Fan Speed and Operation (FOp):
    1U - single speed user selectable fan
    1C - single speed constant fan
    1A - single speed auto fan
    2U - Default, two speed user selectable fan

    2C - two speed constant fan
    2A - two speed auto fan
  Three speed fan only available for fan coil equipment
    3U - three speed user selectable fan
    3C - three speed constant fan
    3A - three speed auto fan
  Compressor Protection (FCp):  Selects the compressor protection and high or low 

speed fan in heating

    CP - Default heat pump, compressor protection and high fan is allowed in heating
    NP - Default fan coil, no compressor protection and high fan is allowed in heating
    CP - compressor protection and high fan is allowed in heating
    nP - no compressor protection and only low fan is allowed in heating
    cP - compressor protection and only low fan is allowed in heating
  Continuous Fan Operation (CFL):  Selects continuous fan operation
    Dis - Default, normal fan operation
    Ena - continuous low fan in auto or economy modes
Step 4:    Press either up or down to reach desired change.
Step 5:    Press fan button to return to program menu.
Step 6:    Press Up or Down arrow until End / Prog appear on the display.
Step 7:    Press fan button to save changes and exit the program mode.  You will need 

to re-enter programming mode to access a different code.

Access Code 79:

Field Programming Mode

Step 1:    Place thermostat into programming mode by pressing and holding the UP 

and DOWN arrows while sliding the °F/°C switch to the opposite side.  00 

will appear on the display.  Do not use the °F/°C switch again until done 

programming.

Step 2:    Press either the up or down arrow button to find the access code 79 then 

press the fan button.

Step 3:    Press either the up or down arrow button to scroll through the menu to 

reach the desired parameter (see below), then press the Fan button.

Step 4:    Press either up or down to reach desired change.
  Exit Menu (Ext):
  Temperature Scale (Unt):  Selects scale parameter that will be shown
    F - Default,°F
    C - °C
  Display Temperature (dSP):  Selects which temperature is shown on display
    SP - Default, display will show setpoint only
    rt - display will show room temperatue unless either up or down arrow button is 

pressed.  Then the display will show   setpoint.

    Srt - display will toggle between room temperature and setpoint.  Display will 

revert to setpoint when either the up or   down arrow button is pressed.

  Temperature Control Mode (HAc):
    USr - Default, switch selectable, heat only, auto changeover or cool only
    AUt - auto mode only
    CL - cool mode only
    Ht - heat mode only
  Off Function Enabled (OFf):  Selects whether or not thermostat can 

be turned off by pressing the fan button